Automatic repositioning
Attention! During the repositioning manoeuvre the current sensor value "SnS"
could be different leading to a momentary increase in the door impact force. At the
end of the manoeuvre, however, it will reset automatically to the chosen value.
If the programmer blocks due to an encoder count error
programmer reset
, when one of the motors has been released
or there is a problem with one of the motors
indicator light will flash simultaneously for 2 seconds and will then switch off for
10 seconds.
After the programmer has been in this condition for 3 minutes it will (after pre-
DISPLAY MODE
Using the PROG button you can access the following functions in
sequence:
- memorising the status of the dip-switches;
- display the status of the command and safety devices;
The status of the security devices
FTCS and CSP are always shown on the display.
Memorising
the
DIP-SWITCH
displaying the firmware version (e.g. "0")
The segments regarding the command status
(LED "ON" = command active) and safety status
(LED "ON" = safety device at rest) light up.
The number of manoeuvres appears on the
display. This number always remains visible until
you change the setting. Once 999999 has been
exceeded the lighting up of the decimal point on
the display equals 1 million + the six figure
number.
In the "test" mode (activated when the motor has
stopped) it is possible to check the status of the
command and safety devices. The warning lights
will activate once, each time a "TA-TC-TAL-TD-
TB-FTCI-FTCS-CSP" command is received. In
this
mode
you
can
communication using the external program,
connected to the CSER connection via cable.
While communication is active dashes will appear
on the display; after 5 seconds of inactivity you
will be moved back to the "test" mode. To return
to the normal mode press the button again "test"
will appear, then wait for 10 seconds.
APL =
Setting the limited opening space :
1 = 1/3 of the distance of gate 1
2 = half the distance of gate 1
3 = 2/3 of the distance of gate 1
4 = the entire distance of gate 1
PRESS
0 sec
PROG
10 seconds after the last
modification you will be
automatically moved out of the
mode and the selected values
will be saved (eg. 4)
Selecting the type of motor
BL1924 = Articulated operator arm
BL3924 = Articulated operator (integrated)
HL2524 = Underground operator
BL224E = Piston type operator
the warning lights and
TB , FTCI,
PRESS PROG
settings
and
PRESS PROG
PRESS PROG
activate
serial
line
PRESS PROG
0 sec
Each time "PROG"
is
pressed
the
number increases
(from 1 to 4).
PRESS
PROG
flashing for 10 seconds) automatically move the gate, slowly, to the completely
closed position (2 times as in the programming procedure) in order to recover the
correct position. At this point the programmer will function normally.
To carry out automatic repositioning without waiting for 3 minutes you may send
a (TA, TC, TAL or TD) command to the programmer. If a "TA" command is given
, after a
the positioning recovery is carried out in the opening direction.
No commands will be accepted during repositioning but the security devices will
cut in and block all movement if they go into alarm.
• To interrupt the repositioning manoeuvre and delay it for another 3 minutes,
press the "PROG" or "TB" button.
- display the number of manoeuvres;
- access the "test" mode;
- set the limited opening distance;
- set the current sensor level;
- selecting the type of motor.
0 sec
0 sec
5 sec
Connect the
programming device
(CSER) and activate it.
PRESS
PROG
PRESS
PROG
Each time "PROG"
is
pressed
number will increase
(from 1 to 3).
0 sec
PRESS
PROG
2
When the
("TA-TC-TD-TAL-TB-FTCI-FTCS, CSP")
inputs are activated the warning lights will light up.
PRESS PROG
0 sec
SNS =
Setting the current sensor:
1 = motor consumption + 2 amp
2 = motor consumption + 3 amps
3 = motor consumption + 3,5 amps
0 sec
the
PRESS PROG
10 seconds after the last modification
you will be automatically moved out
of the mode and the selected values
will be saved (eg. 3)
0 sec