7. Adding or Replacing Internal Batteries
1
Place the UPS System in Bypass Mode or completely turn it off,
depending on preference. (See section 5.4, Operation of Manual
Bypass Switch, or 4.2, Turning the UPS Off.)
2
Remove battery access panel, located on the FRONT of the UPS
system.
3
Disconnect the RED and BLACK cables attached to each internal
battery pack.
4
Remove the battery cartridge fuses from each fuse block.
Save the fuses.
5
Disconnect the BLUE and WHITE jumper cables attached to each
fuse block.
CAUTION!
When disconnecting the jumper cables, pull
them straight away from the fuse block with
even force. Do not wiggle them side-to-side,
as this may damage the connector.
( continued )
2
3
4
5
13