INSTALLATION: CONDENSATE DRAIN
3 cm/m
3 cm/m
MIN Ø 30 mm
The drain system must feature a suitable drain trap in order to:
▪ Ensure free drainage of condensate.
▪ Prevent unwanted intake of air in systems working at negative pressure.
▪ Prevent unwanted outlet of air in pressurised systems.
▪ Prevent bad odours or insects from entering.
P =
P =
Negative pressure
Negative pressure
Condensate collection pan
Condensate collection pan
Negative pressure
H1 (mm) = P + 30 mm
H2 (mm) = H1 = P + 30 mm
H3 (mm) = H1 + H2 = 2P + 60 mm
Where P is the pressure expressed
in mm water column
(1 mmWC = 9.81 Pa)
POWER CONSUMPTION AND CURRENT DRAW
a-HWD2
a-HWD2
102/104
202/204
50 HZ 1,25A 270V 1,25A 270V 1,25A 270V
i-HWD2
i-HWD2
102/104
202/204
50 HZ 1,40A 170V 1,40A 170V 1,40A 170V 1,93A 300V 1,93A 300V 1,93A 300V 2,49A 560V 2,49A 560V 2,49A 560V
Unit condensate drain
Unit condensate drain
Ø 30 mm
Ø 30 mm
Pipe
Pipe
MIN Ø 30 mm
When the work has been completed, make sure the condensate
When the work has been completed, make sure the condensate
drains correctly by pouring some water into the pan
drains correctly by pouring some water into the pan
a-HWD2
a-HWD2
302
402/404
2,7A
570V
i-HWD2
i-HWD2
302
402/404
▪ The water piping should be suitably insulated so as to avoid dripping
during operation in cooling mode.
▪ The condensate drain line must be suitably sized and the piping laid so
that there is a suitable incline (min. 3%) along the entire line, without
rising sections or choking, to ensure correct drainage.
▪ A drain trap should be installed on the condensate drain line.
▪ The condensate drain should be connected to the rainwater drainage
system.
▪ Do not connect to the sewerage system, so as to prevent bad odours
potentially entering the air-conditioned spaces if the water in the drain
trap evaporates.
NOTE: The drain trap must be fitted with a plug at the bottom or must be
able to be easily disassembled for cleaning. The following rules must be
applied for sizing and installing drain traps.
Condensate collection pan
Condensate collection pan
Positive pressure
H1 (mm) = 20 mm
H2 (mm) = P + 30 mm
H3 (mm) = H1 + H2 = P + 50 mm
Where P is the pressure expressed
in mm water column
(1 mmWC = 9.81 Pa)
a-HWD2
a-HWD2
502/504
602
2,7A
570V
2,7A
570V
i-HWD2
i-HWD2
502/504
602
P =
P =
Positive pressure
Positive pressure
a-HWD2
a-HWD2
702/104
802/804
3,9A
840V
3,9A
840V
i-HWD2
i-HWD2
702/704
802/804
a-HWD2
902
3,9A
840V
i-HWD2
902
EN 9

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido