Presence detector for DALi lighting control
Installation and wiring
Please disconnect power completely and read the entire instruction
manual carefully before installation.
Select a proper location
KDP-DALI 01 / KDP-DALI 01-C can be installedat the height of 2 - 3m, it's
recommended to install it at the height of 2.5m to gain the optimal
detection pattern, the detection range can reach up to the diameter of 7m
and cover 360º detection angle (See FIG.2).
Top view
Φ7m
Φ1.2m
Pay attention to the walking direction in the test proceeding.
It is more sensitive to movement across the detector and less
sensitive to movement directly toward to detector which will reduce
the detection coverage (See FIG.3).
More sensitive of movement
walking across the detector
Instructions manual |
Side view
360°
3.5m
Major Motion
Minor Motion
FIG.2
Less sensitive of movement
directly towards to detector
30
0.6m 0.6m
3.5m