The performance of this system is dependent upon the pipe
network. Any extension or modification to the designed
installation may cause improper operation. The operational
effects of such changes need to be verified using the PipeIQ
2 design software.
This equipment and all associated pipe work must be installed in
accordance with all relevant codes and regulations.
PHYSICAL INSTALLATION
Front Panel Labels
The LT NFXI-ASD is shipped without the front panel labels
fixed in place. This allows the installer to choose the language
required for the installation from the Front Panel Labelling Pack.
Figure 2 shows where the labels need to be placed:
SMOKE
LEVEL 1
MODULE 1
FAULT
Figure 2: Placing the Front Panel Labels
When label A is in place, remove the protector from the bottom of
the clear cover to stick the cover down, as shown in Figure 3:
Cable Access
Knock out cable gland holes where required. The
location of the cable gland holes is shown in Figure 1,
represented by the icon:
N200-102-00
Warning
ALARM
PREALARM
10
10
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
SMOKE
1
1
LEVEL 2
MODULE 2
POWER
FAULT
A
Figure 3: Remove Backing to
Stick Cover Down
Figure 4: How to Knock Out Cable
Gland Holes
Mounting the LT NFXI-ASD to the Wall
INDICATES CENTRE OF ASPIRATING PIPES
FAAST LT
HANGING LUGS
FIXING HOLE
Figure 5: Mounting Bracket
POSITION OF BRACKET
PLUMB LINE
OUTER DIMENSION OF UNIT
212 mm
* Minimum clearance required from hinges to open door = 35 mm.
Figure 6: Fasten the mounting bracket to the wall
2
FIXING HOLE
USE FOR PLUMB-LINE
90 mm
99 mm
BASE OUTLINE
144 mm
I56-3947-202
59
41
mm
mm
*
329
mm
*