These guidelines are based upon fire
testing of the generator enclosure and
the manufacturer's requirement for air
flow for proper operation. Local codes
may be different and more restrictive
than what is described here.
60" Minimum
Generator
This drawing supersedes installation instructions in all Carrier air-cooled installation and owner's manuals dated
This drawing supersedes installation instructions in all air-cooled installation and owner's manuals dated previous to May 26, 2007.
previous to May 26, 2007.
Figure 1.10 – Installation Guidelines
No windows or openings in the wall permitted
within 5 feet from any point of the generator.
Existing Wall
60 inches
Minimum Distance
36 inches
Top of Generator
18 inches
36 inches
36 inches
60" Recommended
Minimum From Ends
General Information
60 inches
Clearance from windows,
doors, any openings in the
wall, shrubs or vegetation
over 12" in height
Clearance from the ends and front of the
generator should be 36 inches. This
would include shrubs, trees and any
kind of vegetation. Clearance at the top
should be a minimum of 60 inches from
any structure, overhang or projections
from the wall. The generator should not
be placed under a deck or other
structure that is closed in and would limit
or contain air flow.
18 inches
Minimum
11