3. Installation

3.8 Installation requirements

Recommended protective devices and cable cross-sections
3.8.1 9PXMEZ6Ki use with 9PX6000 or 9PX5000 UPS
• Recommended protective devices
• Recommended cable cross-sections:
9PXMEZ6Ki
Parallel
Operation
9PXMEZ6Ki
Redundancy
Only
3.8.2 9PXMEZ11Ki use with 9PX8000 or 9PX11000 UPS
• Common input source recommended protective devices
Page 12
D curve, 63A for Parallel Operation
D curve, 32A for Redundancy Only
2 poles circuit breaker
Terminal
Wire
position
function
L1
Phase
N
Neutral
(L2)
(Phase)
Ground
L1
Phase
N
Neutral
(L2)
(Phase)
Ground
For Parallel Operation
D curve, 125A if use with 9PX11000 UPS
D curve, 100A if use with 9PX8000 UPS
For Redundancy Only
D curve, 63A if use with 9PX11000 UPS
D curve, 50A if use with 9PX8000 UPS
2 poles circuit breaker
Terminal wire
Minimum input
size rating
wire size rating
4-25 mm
2
10 mm
(12-4 AWG)
4-25 mm
2
6 mm
(12-4 AWG)
Breaker
D Curve
(8 AWG)
63A
2
(10 AWG)
32A
2