Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 76

2.2 Description / Panels

On 9PXMEZ11Ki, it is possible to Bypass the load on a separate Bypass AC source
(see "4.3 9PXMEZ11Ki - with separate Normal and Bypass AC source", page 18 for more details).
9PXMEZ6Ki
9PXMEZ11Ki
UPS output switch
See "5. Operations", page 20.
ModularEasy status detection
A RJ11 signal cable allows to display the following statuses on the UPS display panel:
ModularEasy connection to UPS
Bypass switch position.
614-09354-01_EN
The ModularEasy has a manual Bypass rotary switch with three positions:
UPS: the load is supplied by the UPS.
1
Test: the load is supplied directly by the AC power source,
2
the two UPS are still supplied but their outputs are disconnected from
the load.
Bypass: the load is supplied directly by the AC power source,
3
the two UPS are disconnected from the AC power source.
Lights indicate the ModularEasy power status:
"UPS supply" green light is active when at least one UPS output is
4
available.
"Bypass mode" red light is active when the manual Bypass switch
5
of the ModularEasy is on TEST or BYPASS position. The load is not
protected.
allows to disconnect the output power of the UPS, for UPS maintenance / replacing.
2
:
7
2. Presentation
Input/Output terminal blocks
1
UPS output switch
2
Input/Output cables for
3
connection to UPS1 and UPS2
16A outlets
4
Outlets circuit breaker
5
"Bypass" source input UPS1 and
6
UPS2
Signal cable for 9PXMEZ
7
detection to the UPS
Page 7

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

9pxmez11ki

Tabla de contenido