General Installation Information
1.
Mains Power connection
Use the Mains Connector Terminal for connecting the
mains-supply. A fixed cable or a flexible mains leading
to an earthen mains outlet can be used. In case fixed
wiring is used, insert a dedicated circuit breaker in the
power distribution network. In all cases, the mains
connection has to comply with local regulations.
IMPORTANT:
Disconnect the mains power before opening
!
the cabinet!
Disconnect AC mains plug from AC
Mains wall socket.
Disconnect the mains with the
dedicated circuit breaker.
CAUTION: This unit can be provided with a lead battery
inside. Dispose of this battery according to chemical
waste regulations only.
2.
Mounting
The unit is mounted with screws or bolts through the
four mounting holes in the base.
Ensure that the unit is mounted on a flat, solid, vertical
surface such that the base will not flex or warp when
the mounting screws/bolts are tightened.
Leave a 50-mm clearance between equipment
enclosures mounted side by side and 25 mm between
the enclosure and the sidewalk.
The battery mounting facility inside the housing is only
useful for steady state use of the control panel. Remove
the battery for transport of the control panel.
Ensure that the wire terminals are isolated. Use tie
wraps to prevent contact with any other wires or circuits
in case wires break.
3.

General installation guidelines

The ATS1201 has been designed, assembled and
tested to meet the requirements related to safety,
emission and immunity with respect to environmental
electrical and electromagnetic interference, as of
current relevant Standards.
If the following guidelines are followed, the system will
give many years of reliable service.
In addition to the following guidelines, during the
installation of the ATS1201, it is essential to follow any
country dependent installation requirements of local
applicable standard. Only a qualified electrician or other
suitable trained and qualified person should attempt to
wire this system to the mains or to the public telephone
network.
4
Or
1.
Ensure that there is a good earth available for
the alarm system.
2.
Maintain a separation between the low voltage
and mains supply cables. Use separate points of
cable entry to the control panel cabinet.
3.
If, the upper and/or lower cabinet entry cable
holes are used to route wiring into the control
panel, always use a proper pipe fitting system by
means of an appropriate conduit and junction
box. For this purpose, use only materials of
suitable flammability class (HB or better).
4.
For Mains Power connection, use the mains
connector terminal either through a permanent
wiring or a flexible mains cable to an earthed
mains outlet. Always use cable ties to fix mains
cable, at the dedicated fixing point provided near
the mains terminal connector.
a.
In case of permanent fixed wiring, insert
an easily accessible, dedicated bipolar
circuit breaker in the power distribution
network.
b.
Never attempt to solder mains connection
wires end where they will be wired to the
terminal connectors.
5.
Avoid loops of wire inside the control panel
cabinet and route cables so that they do not lie
on top or underneath the printed circuit board.
The use of cable ties is recommended and
improves neatness of the wiring within the box.
6.
The battery used with this unit, must be made of
materials of suitable flammability class (HB or
better).
7.
Any circuit connected either directly to the on
board relay's contact or to external relay's
contact through the on board electronic output,
must be of SELV (Safety extra low voltage)
operating circuit.
a.
Mains switching relay must not be fitted
inside the control panel cabinet
b.
Always place a suppression diode (e.g. a
1N4001) across the relay coil
c.
Use only relay with good insulation
between the contacts and the coil.
8.
The minimum clearance between equipment
closures is 50 mm (between equipment vents).
9.
Only use units in a clean environment and not in
humid air.