Elko EP HRN-41 Manual Del Usuario página 3

Ocultar thumbs Ver también para HRN-41:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 17
ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: elko@elkoep.com
www.elkoep.com
Made in Czech Republic
02-13/2017 Rev.: 0
Characteristics
• relay designed for monitoring DC and AC voltage in three ranges
• the relay controls the size of the voltage in two independent levels (Umin, Umax)
• setting the monitored level Umax (in % of range)
• setting the monitored level Umin
(in % of range - for HRN-42 -function WINDOW),
(in % of the set upper limit - for HRN-41 - function HYSTERESIS)
• adjustable function "MEMORY"
• function of second relay (independently / in parallel)
• adjustable delay for eliminating short-term outages and surges for every level
independently
• galvanically separated power supply from monitoring inputs
• output contact 2x switching 16 A / 250 V AC1 for each monitored voltage level
• in 3-MODULE design, fi xing to DIN rail
Description
1
2
3
4
5
cos φ ≥ 0.95
Type of load
AC1
Mat. contacts AgNi,
contact 16A
250V / 16A
Type of load
AC13
Mat. contacts AgNi,
contact 16A
250V / 6A
1. Supply voltage terminals
6
2. Supply indication
7
8
3. Indication Umax
9
4. Output indication
10
5. Indication Umin
11
6. Current voltage terminals
12
7. AC/DC
13
- if alternating current voltage is connected when measuring DC or direct current voltage is connected when measuring AC, or if
14
there is incorrect polarity of DC, a polarity error is reported - both red LEDs fl ash and relays are open
15
8. Memory
- when the memory is switched on, the indication of an error status is maintained until the moment of reset by means of a button
(if in between, the OK status occurs)
9. Output
- position 1 - both relays work simultaneously (they open in error status)
16
- position 2 - the relays work independently - relay 15-16-18 corresponds to the upper level (Umax), relay 25-26-28 corresponds to
the lower level (Umin)
10. Hysteresis - setting the hysteresis upon returning from an error state
11. t1 - time delay for Umax
12. Adjusting upper level - Umax
13. Button RESET
14. t2 - time delay for Umin
15. Adjusting bottom level - Umin
16. Output contact
M
M
AC2
AC3
uncompensated
250V / 5A
250V / 3A
230V / 3A (690VA)
K
AC14
AC15
250V / 6A
250V / 6A
HRN-41
HRN-42
Monitoring voltage relay
Symbol
Connection
AC5a
AC5a
compensated
x
M
DC3
DC1
24V / 6A
24V / 16A
1 / 2
A1
16
18 26 28
C
B1
U
B2
B3
A2
15
25
100 - 500 V
32-160 V
Un
10-50 V
A1 A2 C B1 B2 B3
16 15 18 28 25 26
HAL.230V
AC5b
AC6a
800W
x
250V / 3A
M
DC5
DC12
24V / 4A
24V / 16A
EN
AC7b
AC12
250V / 10A
DC13
DC14
24V / 2A
24V / 2A

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Hrn-42

Tabla de contenido