Technical Parameters - Elko EP HRN-41 Manual Del Usuario

Ocultar thumbs Ver también para HRN-41:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 17

Technical parameters

Supply
Supply terminals:
Supply voltage:
Consumption max.:
Max. dissipated power
(Un + terminals):
Supply voltage tolerance:
Measuring
AC/DC 10 - 50 V AC/DC 32 - 160 V AC/DC 100 - 500 V
Ranges:*
(AC 50 - 60 Hz)
Terminals:
Input resistance:
Max. permanent current:
Inrush overload < 1ms:
Time delay for Umax:
Time delay for Umin:
Accuracy
Time deviation:
Repeat accuracy:
Dependance on temperatur.:
Tolerance of limit values:
Hysteresis (from fault to o.k.):
Output
Number of contacts:
Rated current:
Switching capacity:
Inrush current:
Switching voltage:
Output indication:
Mechanical life:
Electrical life (AC1):
Other information
Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting:
Protection degree:
Overvoltage cathegory:
Pollution degree:
2
Max. cable size (mm
):
Dimensions:
249 g (8.8 oz.) (110 V, 230 V, 400 V); 146 g (5.1 oz.) (24 V)
Weight:
Standards:
* Only one of the inputs can be connected.
HRN-41
HRN-42
A1 - A2
AC 110 V, AC 230 V, AC 400 V or AC/DC 24 V
(AC 50 - 60 Hz)
5 VA / 2.5 W (AC 110 V, AC 230 V, AC 400 V),
2 VA / 2.5 W (AC/DC 24 V)
7 W (110 V, 230 V, 400 V),
6 W (24 V)
-15 %; +10 %
(AC 50 - 60 Hz)
(AC 50 - 60 Hz)
B1 - C
B2 - C
212 kΩ
676 kΩ
2.12 MΩ
100 V
300 V
250 V
700 V
adjustable 0.1 - 10 s
adjustable 0.1 - 10 s
5%
< 1%
< 0.1 % / °C
5 %
selectable 5 % / 10 % from range
2x changeover / SPDT (AgNi / Silver Alloy)
16A / AC1
4000 VA / AC1, 384 W / DC
30 A < 3 s
250 V AC / 24 V DC
yellow LED
7
3 x 10
0.7 x 10
5
-20 °C to +55 °C (-4 °F to 131 °F)
-30 °C to +70 °C (-22 °F to 158 °F)
4 kV (supply - output)
any
DIN rail EN 60715
IP40 from front panel / IP20 terminals
III.
2
solid wire max. 1x 2.5 or 2x 1.5 /
with sleeve max. 1x 1.5 (AWG 12)
90 x 52 x 65 mm (3.5˝ x 2˝ x 2.6˝)
EN 60255-6, EN 61010-1
Function
Un
Umax
U
Umin
t1
15-18
25-28
15-18
25-28
RESET
LED > U
LED <U
LED
B3 - C
t = 0.1s
600 V
- if the value of the monitored voltage is in the zone between the set upper and lower
1 kV
levels, the status OK occurs - both relays are closed and the yellow LED illuminates. If
the value of the monitored voltage is outside the set limits (> Umax or < Umin), an error
state occurs.
- when moving to an error state U > Umax, it times the delay t1 and a red LED > U
simultaneously fl ashes. After the t1 time elapses, the red LED > U illuminates and the
relevant relay opens.
- when moving to an error state U < Umin, it times the delay t2 and a red LED < U
simultaneously fl ashes. After the time t2 elapses, the red LED < U illuminates and the
relevant relay opens.
- when moving from the error status to the OK status, the relevant red LED immediately
goes out, and the corresponding relay closes.
Warning
Device is constructed for connection for 1-phase main or DC circuits (according to types, it
is necessary to observe voltage ranges) and must be installed in accordance with regula-
tions and standards applicable in a country of use. Installation, connection and setting
can be done only by a person with an adequate electro-technical qualifi cation which has
read and understood this instruction manual and product functions. The device contains
protections against over-voltage peaks and disturbing elements in the supply main. Too
ensure correct function of these protection elements it is necessary to front-end other
protective elements of higher degree (A, B, C) and screening of disturbances of switched
devices (contactors, motors, inductive load etc.) as it is stated in a standard. Before you
start with installation, make sure that the device is not energized and that the main switch
is OFF. Do not install the device to the sources of excessive electromagnetic disturbances.
By correct installation, ensure good air circulation so the maximal allowed operational
temperature is not exceeded in case of permanent operation and higher ambient tem-
perature. While installing the device use screwdriver width approx. 2 mm. Keep in mind
that this device is fully electronic while installing. Correct function of the device is also
depended on transportation, storing and handling. In case you notice any signs of dam-
age, deformation, malfunction or missing piece, do not install this device and claim it at
the seller. After operational life treat the product as electronic waste.
2 / 2
hysteresis
hysteresis
t2
<t
<t
t1
memory ON (DIP2)
hysteresis