baltur SPARK 18W Manual De Instrucciones página 21

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

CONTROLS IN CASE OF OPERATION PROBLEMS
Extraneous light / advanced ignition
During the pre-ventilation and/or pre-starting phase
there shall be no flame signal. Should the signal
be present, for example for advanced ignition due
to bad tightness of the electrovalve, external
lighting, short-circuit in the photo-resistance or in
the connecting cable, a breakdown in the flame
signal amplifier, and so on., when the pre-ventilation
and safety time has elapsed, the control-box brings
the burner to the emergency stop and cuts off fuel
inflow even during the safety time.
No flame
If there is no flame at the end of the safety time,
the control-box stops the burner immediately.
No flame during operation
If there is no flame during operation, the control-
box cuts off fuel and automatically repeats a new
starting program: once the "t4" time has elapsed,
the starting program is over.
Every safety stop of less than 1 second switches
off voltage to terminals 3 - 8 and 11: in the same,
by means of terminal 10, it is possible to provide
a remote signal of emergency stop. Resetting of the control-box is possible after approx. 50 seconds
of emergency stop.
Program Legend
Control-box output signals
Input signals required
A' Beginning of starting cycle for burners
with light-oil pre-heater "OH"
A
Beginning of starting cycle for burner
without light-oil pre-heater
B
Flame presence
C
Normal operation
D
Adjustment stop by "R"
Execution
Tension
V ~
220 V / 240 V
Normal
220 V / 240 V
LIGHT OIL BURNER
MODEL SPARK
tw Light-oil pre-heating time until
t1 Pre-ventilation time
t3 Pre-starting time
t2 Safety time
t3n Post-starting time
t4 Time interval between flame
Safety at
Type
Pre-ventilation
low voltage
Without
base
-
LOA21.171B27
LOA24.171B27
operation consent by
contact "OW"
presence and connection of 2nd
valve to terminal 5
Safety
Pre-starting
time
t1
t3
t2
13 s
13 s
10 s
13 s
13 s
10 s
21
Time
Post-starting
interval
t3n
BV1 - BV2 t4
max
15 s
15 s
15 s
15 s

Publicidad

Tabla de contenido
loading

Tabla de contenido