FM / CSA Installation drawing

Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D
OR
Class I, Zone 0, IIC
1
1
2
5350B
5350B
Approved
Termi-
6
3
6
nation
5
4
5
SENSOR
SENSOR
Terminal 3, 4, 5, 6
Vt or Uo : 5,71 V
It or Io : 8,4 mA
Pt or Po : 12 mW
Ca or Co : 40 uF
La or Lo : 200 mH
Terminal 1,2
Class I, Zone 0, Ex ia IIC, Entity / FISCO
IS, Class I, Division 1, Group A, B, C, D
Entity / FISCO
Barrier
Linear
Trapezoid
Suitable for
Suitable for
type:
barrier
barrier
FISCO
systems
T1..T4:
Ta  +85C
Ta  +75C
Ta  +85C
T5:
Ta  +70C
Ta  +65C
Ta  +60C
T6:
Ta  +60C
Ta  +45C
Ta  +45C
Vmax or Ui
30 V
30 V
17.5 V
Imax or Ii
120 mA
300 mA
250 mA
Pi
0.84 W
1.3 W
2.0 W
Ci
2.0 nF
2.0 nF
2.0 nF
Li
1 H
1 H
1 H
See Installation notes.
Revision date:
Version /Revision
2009-09-29
V3/R0
5350V111
5350QE01
WWW.PRELECTRONICS.COM
Unclassified Location
Associated Apparatus
Barrier or
FISCO Supply
with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
Isc or Io < Imax or Ii
1
2
2
Po < Pi
5350B
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
3
6
3
4
5
4
This device must not be
connected to any
associated apparatus
SENSOR
which uses or generates
more than 250 VRMS
FISCO
systems
Ta  +85C
Ta  +60C
Ta  +45C
15 V
900 mA
5.32W
2.0 nF
1 H
Page:
1/6
LERBAKKEN 10, 8410 RØNDE DENMARK.
Hazardous (Classified) Location
Class I,Division2, Groups, A,B,C,D
OR
Class I, Zone 1, IIC
1
1
2
5350B
5350B
Approved
Termi-
6
3
6
nation
5
4
5
SENSOR
SENSOR
Terminal 3, 4, 5, 6
Vt or Uo : 5,71 V
It or Io : 8,4 mA
Pt or Po : 12 mW
Ca or Co : 40 uF
La or Lo : 200 mH
Entity Parameters
Terminal 1, 2
Class I, Zone 1, Ex ib IIC
Entity / FISCO
Barrier type:
Rectangular
FISCO
barrier
Segment
coupler
T1..T4:
Ta  +85C
Ta  +85C
T5:
Ta  +75C
Ta  +75C
T6:
Ta  +60C
Ta  +60C
Vmax / Ui
30 V
17.5 V
Imax or Ii
250 mA
any
Pi
5.32 W
any
Ci
2.0 nF
2.0 nF
Li
1 H
1 H
See Installation notes.
Revision date:
Version /Revision
2009-09-29
V3/R0
5350V111
5350QE01
WWW.PRELECTRONICS.COM
Unclassified Location
Associated Apparatus
Barrier with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
1
2
2
La or Lo > Li + Lcable
5350B
or
FISCO Supply
3
6
3
This device must not be
4
5
4
connected to any
associated apparatus
which uses or generates
SENSOR
more than 250 VRMS
Nonincendive Field Wiring
parameters
Terminal 1, 2
NI, Class I, Division 2, Group A, B, C, D
NIFW/ FNICO
T1..T4:
Ta  +85C
Ta  +85C
T5:
Ta  +75C
Ta  +75C
T6:
Ta  +60C
Ta  +60C
Vmax / Ui
30 V
17.5 V
Pi
5.32 W
any
Ci
2.0 nF
2.0 nF
1 H
1 H
Li
For a current-controlled circuit the
parameter Imax is not required and need
not be aligned with the parameter Isc or It
of the barrier or associated nonincendive
field wiring apparatus.