To Connect The Shut-Off Valve; To Connect The Electricity Meters - Daikin Altherma 3 H W Serie Manual De Instalación

Ocultar thumbs Ver también para Altherma 3 H W Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 110
4 Installation
Model (power
Connections to backup heater power
supply)
*6V (6V: 1N~ 230 V)
SWB
F1B
1N~, 50 Hz
230 V AC
*6V (6T1: 3~ 230 V)
K5M
SWB
F1B
Q1DI
3~, 50 Hz
230 V AC
*9W (3N~ 400 V)
SWB
F1B
Q1DI
3N~, 50 Hz
400 V AC
F1B  Overcurrent fuse (field supply). Recommended fuse:
4‑pole; 20 A; curve 400 V; tripping class C.
K5M Safety contactor (in the switch box)
Q1DI Earth leakage circuit breaker (field supply)
SWB Switch box
X6M Terminal (field supply)
Installation manual
12
supply
2
4
6
14
K5M
1
3
5
13
X6M
1
3
5
7
I
I
I
I
2
4
6
8
Q1DI
L
N
2
4
6
14
1
3
5
13
X6M
1
3
5
7
I
I
I
I
2
4
6
8
L1 L2 L3
2
4
6
14
K5M
1
3
5
13
X6M
1
3
5
7
I
I
I
I
2
4
6
8
L1 L2 L3
N
NOTICE
Do NOT cut or remove the backup heater power supply
cable.
4.4.5

To connect the shut-off valve

INFORMATION
Shut-off valve usage example. In case of one LWT zone,
and a combination of underfloor heating and heat pump
convectors, install a shut-off valve before the underfloor
heating to prevent condensation on the floor during cooling
operation. For more information, see the installer reference
guide.
1 Connect the valve control cable to the appropriate terminals as
shown in the illustration below.
NOTICE
Wiring is different for a NC (normally closed) valve and a
NO (normally open) valve.
NO
21 28
X2M
X1M
M2S
2 Fix the cable with cable ties to the cable tie mountings.
4.4.6

To connect the electricity meters

INFORMATION
In case of an electricity meter with transistor output, check
the polarity. The positive polarity MUST be connected to
X5M/6 and X5M/4; the negative polarity to X5M/5 and
X5M/3.
1 Connect the electricity meters cable to the appropriate terminals
as shown in the illustration below.
X5M
S2S S3S
2 Fix the cable with cable ties to the cable tie mountings.
NC
21 29
X2M
X1M
M2S
EABH/X16DF6V+9W
Daikin Altherma 3 H W
4P644479-1 – 2020.12

Publicidad

Tabla de contenido
loading

Tabla de contenido