1) GENERAL INFORMATION
The PERSEO CBD 230.P SD control board comes with standard factory settings.
Any change must be made using the programmer with built-in display.
Fully supports EELINK protocol.
Its main features are:
Control of up to 4 bollards: STOPPY MBB -500 C. - STOPPY MBB 219-700 C.
Note: Bollards of the same type must be used.
- Separate inputs for safety devices
- Built-in radio receiver rolling code with transmitter cloning.
The board has a terminal strip of the removable kind to make maintenance or
replacement easier. It comes with a series of prewired jumpers to make the installer's
job on site easier. If the terminals are being used, remove the relevant jumpers.
2) TECHNICAL SPECIFICATIONS
Power supply*
Motor outpu
Flashing light/traffic light
Accessory output:
LED Output
Buzzer Output
Aux Contact
2nd Ch rx Contact
Low voltage/mains insulation
Operating temperature range
Thermal overload
Dielectric rigidity
Dimensions
Fuses
3) RECEIVER TECHNICAL SPECIFICATIONS
Max. n° of radio transmitters that
can be memorized
POWER TERMINAL BLOCK J2
Terminal
L N E
MOTA
COM
M
MOTB
CAP
CAP
EV
EV
SL
SL-COM GR-RD-COM
GR
RD
INSTALLATION MANUAL
220-230V 50-60Hz (*)
220-230V~; 3A max
220-230V~; 40W
24V~; 1A max
24V~ 0,1A max
24V~ 0,1A max
Max 24V 0,5A
Max 24V 0,5A
>2Mohm 500Vdc
-20° C+ 60° C
protection built into motor
mains/LV 2500Vac for 1 second
See Fig.B
See Fig.C
2048
Single-phase power supply
L Live
N Neutral
E Earth
Motor connection
MOTA Motor opening
COM Motor Common
MOTB Motor closing
Motor capacitor
Not used
SL Flashing Light - max. 40W
SL-COM/ gR-RD-COM 230V
gR green Light - max. 40W
RD Red Light - max. 40W
Frequency
Code by means of
N° of combinations
RADIO CHANNEL FUNCTIONALITY
PR1
PR 2
(* other voltages to order)
Usable transmitter versions:
All ROLLING CODE transmitters compatible with
3) TUBE ARRANGEMENT Fig. A
4) CONTROL PANEL DIMENSIONS Fig.B
5) TERMINAL BOARD WIRING Fig. C
WARNINGS - When performing wiring and installation, refer to the standards in
force and, whatever the case, apply good practice principles.
Wires carrying different voltages must be kept physically separate from each other,
or they must be suitably insulated with at least 1mm of additional insulation.
Wires must be secured with additional fastening near the terminals, using devices
such as cable clamps.
All connecting cables must be kept far enough away from the dissipater.
WARNING! For connection to the mains power supply, use a multicore
cable with a cross-sectional area of at least 3x1.5mm2 of the kind provided
for by the regulations in force.
To connect the motors, use a cable with a cross-sectional area of at least 1.5mm2
of the kind provided for by the regulations in force. By way of example, if the
cable is run outside (unprotected), it must be at least type H07RN-F, while if it is
run inside (in a raceway), it must be at least type H05 VV-F.
Description
220-230V 50/60Hz
, with earth cable
433.92 MHz
Rolling-code algorithm
4 billion
Select the command from parameter
R1
Closes the relay contact on the terminal
block J4 "2nd CH RX"
PERSEO CBD 230.P SD -
15