Battery Replacement

Under normal conditions, the original battery in your UPS will last several years. Battery replacement should only be performed by qualified
personnel. Refer to "Battery Warnings" in the Safety section for complete battery safety information.
Your UPS requires two Tripp Lite RBC51 (for ECO1300LCD and ECO1500LCD) or one RBC51 (for ECO1000LCD) replacement battery cartridges.
For further information about replacement compatibility and ordering, visit Tripp Lite on the Web at www.tripplite.com/products/battery-finder.
Battery replacement must be done using the same battery type and quantity: 12V DC sealed lead acid, 6 cell, and in
compliance with UL 1989.
CAUTION: Risk of energy hazard. Before replacing batteries, remove conductive jewelry such as chains, wrist watches and rings.
High energy passing through conductive materials may cause severe burns.
Battery specification: 12V DC, 9Ah.
To Replace the Batteries:
1. Remove the front panel by sliding it down and away from the UPS.
3. Connect the new batteries in exactly the same manner as the
old ones: positive (red) connectors together and negative (black)
connectors together. Carefully push the batteries back into the
UPS.
UPS and Battery Recycling
Please recycle Tripp Lite Products. The batteries used in Tripp Lite products are sealed Lead-Acid batteries. These batteries are highly
recyclable. Please refer to local codes for disposal requirements.
Call Tripp Lite for recycling info at 1.773.869.1234.
Go to the Tripp Lite Website for up-to-date information on recycling the batteries or any Tripp Lite product.
Please follow this link: http://www.tripplite.com/support/recycling-program/
2. Carefully pull the old batteries from the UPS and disconnect them.
4. Reinstall the battery support bar and replace the front panel.