Installation Check - Honeywell HM700A1000 Manual Del Usuario

Ocultar thumbs Ver también para HM700A1000:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

START UP

Installation Check

Before turning on power to the HM700, inspect the installation to ensure that it was carried out correctly.
2X DUCT HEIGHT
FROM FAN OR
TRANSITION
AIR PROVING
(OPTIONAL)
IN SERIES BETWEEN
TERMINALS 1 AND 2.
JUMPER BETWEEN
TERMINALS 1 AND 8
MUST BE REMOVED.
STEAM LINE
- ADEQUATE SLOPE
- NO RESTRICTIONS
- NO KINKS IN HOSE
- CONDENSATE TRAPS
ON LONG RUNS
MOUNTING
- UNIT LEVEL
- SCREWS INTO
STRUCTURAL
MEMBER
SPEC LABEL
AIR GAP
CAUTION
Equipment Damage Hazard
Do not leave the On/Off/Drain switch in the drain
position for more than one complete drain cycle. The
drain valve solenoid may heat up and result in damage
to the valve and its wiring.
Do not attempt to drain with no water in system.
4 FEET (1219) MINIMUM
2/3 DUCT
HEIGHT
(20 CM)
MINIMUM
P TRAP
WITH 12 IN (30 CM)
MINIMUM DROP
1/2 IN. LINE (MINIMUM) TO WITHIN 4 FT (1.2 M). 30-100 PSIG
Fig. 19. Installation check.
10 FEET (3 M) MINIMUM
8
BEND, OR OTHER
OBSTRUCTION
FUSED DISCONNECT
CORRECT VOLTAGE / AMPS /
PHASE PER SPEC LABEL
(OPTIONAL)
NOTE: U OR HUM TERMINALS IN SERIES BETWEEN TERMINALS 1 AND 2
DRAIN LINE SHOULD BE ROUTED TO ALLOW FREE FLOW OF
WATER. ENSURE ADEQUATE SLOPE, NO TRAPS, AND NO KINKS.
On/Off
The HM700 is factory-configured to operate as an On/Off
humidifier. It will run when 24 VAC from terminal 1 is fed back
into terminal 2 through an On/Off humidistat and other
security devices in series.
13
HIGH LIMIT
ON/OFF
(OPTIONAL)
IN SERIES BETWEEN
TERMINALS 1 AND 2.
JUMPER BETWEEN TERMINALS
1 AND 8 MUST BE REMOVED.
HUMIDITY CONTROL
IN RETURN DUCT OR
LOCATION WHICH
REPRESENTS HUMIDIFIED
SPACE (NO DRAFTS, NOT
BY DOOR, NOT BY DIFFUSER)
HM700A1000
M35807
33-00118EFS—03