11 GPD
11 GPD
22 GPD
a
In the table above, 11 GPD indicates a steam humidifier configured to run on 120 V and 22 GPD indicates a steam humidifier
configured to run on 240 V.
LOCATION
Mount on a suitable wall or vertical surface. Do not sit the unit
on the floor. Allow clearances required for plumbing and
electrical connections. Clearance dimensions shown are for
reference only and are the minimum required for maintenance
of the humidifier. Consult local and national codes before final
location and installation. Honeywell does not accept
responsibility for installation code violations.
• Install only in areas with ambient temperature 41 to 104 °F
(5 to 40 °C) and relative humidity 5 to 95 %.
• When possible install below the steam distributor. Take
care to provide proper steam line routing and proper
condensate traps.
• DO NOT locate the humidifier any further then absolutely
necessary from the steam distributor location as net output
will be reduced as a result of heat loss through the steam
line.
• When possible, mount the HM700 humidifier at a height
convenient for servicing.
KEYHOLE
HOLE
Table 4. Steam humidifier(s) necessary for application.
3
3
11 GPD
22 GPD
INSERT SCREW LEAVING
1/4 IN. (6 MM) EXPOSED.
HANG UNIT, THEN
TIGHTEN SCREW.
INSTALL SECOND
SCREW AFTER
HANGING
HUMIDIFIER
Fig. 3. Mounting with keyholes.
3
3
11 GPD
11 GPD
11 GPD (x3)
11 GPD (x3)
or
or
22 GPD (x2)
22 GPD (x2)
NOTE: Do not mount on hot surfaces, where freezing
can occur, vibrating surface, or floor.
Mounting with Keyholes
1. The HM700 humidifier is wall mounted using a keyhole
located on the back of the unit cabinetry.
2. Use #8 x 2 in. (5 cm) screws mounted into 2x4 studs or
better. 2 screws are needed, one for hanging the unit
and one for securing so it will not lift off the keyhole.
3. Install the top screw so that 1/4 in. (6 mm) is exposed.
Raise the unit and place the screw head through the
keyhole.
4. Make sure the unit is level and then insert and tighten
the second screw through the bottom hole. Tighten the
top screw. See Fig. 3.
NOTE: Use screws longer than 2 in. (5 cm) if drywall or
other spacer is present.
#8 X 2 IN. (5 CM)
WOOD SCREWS
5
a
3
3
or
or
22 GPD (x1)
11 GPD (x3)
or
22 GPD (x2)
22 GPD (x2)
or
or
22 GPD (x2)
22 GPD (x3)
2X4 OR OTHER
STRUCTURAL
MEMBER
M35759
HM700A1000
3
33-00118EFS-03