* Usually an electrical permit and services of a
licensed electrician are required.
* If the supply cord and/or the plug should need to
be replaced, it should only be done by a qualified
service engineer.
* In accordance with the requirement of the IEC
standard, the maximum permissible system
impedance (Zmax) at the interface point of the
power supply to be connected with this icemaker
must be 0.17+j0.10 ohm (FM-600/FMN-440) or
0.2908+j0.18175 ohm (FM-481/251). Determine
in consultation with the supply authority, if
necessary, that the icemaker is connected only to
a supply of 0.17+j0.10 ohm (FM-600/FMN-440)
or 0.2908+j0.18175 ohm (FM-481/251) or less.
[FM-600/FMN-440]
* The fixed wiring must incorporate a means for
disconnection from the supply having a contact
separation of at least 3 mm in all poles.
[FM-481/251]
For the U.K. and the Republic of Ireland only
* The wires in the mains lead are coloured in
accordance with the following code:
Green & Yellow = Earth
Blue = Neutral
Brown = Live
As the colours of the wire in the mains lead
of this appliance may not correspond with the
coloured markings identifying the terminals in
your plug, proceed as follows:
The wire which is coloured Green-and-Yellow
must be connected to the terminal in the plug
which is marked with the letter E or by the symbol
or coloured Green or Green-and-Yellow. The
wire which is coloured Blue must be connected
to the terminal which is marked with the letter N
or coloured Black. The wire which is coloured
Brown must be connected to the terminal which
is marked with the letter L or coloured Red.
* Should the socket outlets in the installation site
not be suitable for the plug supplied with your
product, the plug must be removed (cut off if it is
moulded on plug) and an appropriate plug fitted.
If the non-rewirable plug has been cut from the
power supply cord, it must be disposed of. There
should be no attempt to reuse it. Inserting such a
plug into a socket elsewhere presents a serious
risk of electrical shock.
* The non-rewirable plug must never be used
without a fuse cover being fitted.
The correct replacement for the detachable fuse
cover is identifiable from the manufacturer's
reference number stamped on the plug.
Supply of replacement fuse covers can be
obtained from Hoshizaki Parts/Service Centres.
Fuses should be rated at 13A (FM-481) or 10A
(FM-251) and approved to BS 1362.
5. WATER SUPPLY AND DRAIN
CONNECTIONS
WARNING
Connect to potable water supply only.
* The connections to the mains water supply
must be made in accordance with the countries'
current requirements of the Water Supply or
Water Fittings Regulations.
* Water supply pressure should be minimum 0.05
MPa (0.5 bar) and maximum 0.78 MPa (8 bar).
If the pressure exceeds 0.78 MPa (8 bar), use a
proper pressure reducing valve. Do NOT throttle
back the supply tap.
* A plumbing permit and services of a licensed
plumber may be required in some areas.
* The icemaker drain is gravity flow, so ensure
drain pipe has an adequate pitch or fall.
* Water should drain into an open trap.
* On water-cooled model, a back flow preventer
may be required in the cooling water circuit.
* Be sure to use the new hose-sets supplied with
the appliance. Do not reuse any old hose-sets.
1) [Water-Cooled Model Only]
By means of a suitable spanner or wrench,
tighten the 1/2-3/4 nipple (accessory) into the
Rc1/2 fitting and the 3/4-3/8 nipple (accessory)
into the Rc3/8 fitting on the rear of the icemaker
as indicated. P.T.F.E. tape and/or a suitable
sealing compound should be used to obtain a
leak free joint.