Idiomas disponibles

Quick Parameter Reference, Faults and Alarms
Param.
Function
P0755 Profibus Writing #8
P0918 Profibus Address
P0922 Profibus Teleg. Sel.
P0963 Profibus Baud Rate
P0967 Control Word 1
P0968 Status Word 1
P1000 SoftPLC Status
P1001 SoftPLC Command
P1002 Scan Cycle Time
P1010 SoftPLC Parameter 1
P1011 SoftPLC Parameter 2
P1012 SoftPLC Parameter 3
P1013 SoftPLC Parameter 4
P1014 SoftPLC Parameter 5
20 | CFW500
Adjustable
Range
0 to 1199
1 to 126
2 = Standard Telegram 1
3 = Telegram 103
4 = Telegram 104
5 = Telegram 105
6 = Telegram 106
7 = Telegram 107
8 = Telegram 108
0 = 9.6 kbit/s
1 = 19.2 kbit/s
2 = 93.75 kbit/s
3 = 187.5 kbit/s
4 = 500 kbit/s
5 = Not Detected
6 = 1500 kbit/s
7 = 3000 kbit/s
8 = 6000 kbit/s
9 = 12000 kbit/s
10 = Reserved
11 = 45.45 kbit/s
Bit 0 = ON
Bit 1 = No Coast Stop
Bit 2 = No Quick Stop
Bit 3 = Enable Operation
Bit 4 = Enable Ramp Generator
Bit 5 = Reserved
Bit 6 = Enable Setpoint
Bit 7 = Fault Acknowledge
Bit 8 = JOG 1 ON
Bit 9 = Reserved
Bit 10 = Control By PLC
Bit 11 to 15 = Reserved
Bit 0 = Ready to Switch ON
Bit 1 = Ready to Operate
Bit 2 = Operation Enabled
Bit 3 = Fault Present
Bit 4 = Coast Stop Not Active
Bit 5 = Quick Stop Not Active
Bit 6 = Switching ON Inhibited
Bit 7 = Warning Present
Bit 8 = Reserved
Bit 9 = Control Requested
Bit 10 to 15 = Reserved
0 = No App.
1 = Installing App.
2 = Incompat. App.
3 = App. Stopped
4 = App. Running
0 = Stop Program
1 = Run Program
2 = Delete Program
0 to 65535 ms
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
Factory
User
Propr.
Setting
Setting
0
1
2
ro
ro
ro
0
ro
0
ro
0
0
0
0
0
Groups Page
NET
17-5
NET
17-5
NET
17-5
NET
17-5
NET
17-5
NET
17-5
READ,
18-1
SPLC
SPLC
18-1
READ,
18-1
SPLC
SPLC
18-2
SPLC
18-2
SPLC
18-2
SPLC
18-2
SPLC
18-2

Publicidad