Space Required Around Unit
Refer diagram below for the space required around the unit. Note that:-
l
All dimensions shown are in mm.
l
All space value shown are minimum clearance required for the unit.
l
Unit shown in the diagram is UATYQ250. Other models shall follow the same clearance.
Blower & motor
service
Air fi lter
service
Evaporator coil
service
Additional space or clearance is required when economizer kit is installed. Whenever the unit is equipped with
economizer kit, the space required around the unit with economizer kit shall follow the diagram below:-
Blower & motor
service
Air fi lter
service
Evaporator coil
& economizer
kit service
Air fi lter for economizer
kit service
16
Electrical control
circuit service
1200
Condenser
air inlet
Compressor service
Electrical control
circuit service
1200
Condenser
air inlet
Compressor service
1200
Fresh air
inlet
X
Condenser
air outlet
Condenser
air outlet
X : No obstacles and no accumulation of snow or
water shall be allowed in this area.