NETWORKS AND CONNECTIVITY

CONNECTION TO SUPERVISION SYSTEM
(EXTERNAL SUPERVISOR SYSTEM
SOLUTION)
Connection is possible for version External
Supervisor System 3.10 or higher.
Using serial port RS485 it is possible to connect FWECSA
controllers (up to 247) to a management software that uses
standard MODBUS RTU as a communication protocol, with
the following characteristics:
• settable baudrate (defualt: 9600);
• no parity
• 8 bits of data
• 1 bit of stops
Inside a supervision network, each FWECSA controller acts
as a SLAVE towards the centralised management system
which constitutes the network MASTER (figure 01).
Once the network has been wired, it is necessary to configure
each FWECSA controller. Press PRG to access the MENU
and then enter sub-menu "Networks and connections"
(password = 20). Set the SETUP RS485 parameters as
follows:
• MST/SLV = "Slave from SPV"
• Protocol = "Modbus"
• Serial address = set a value between 1 and 255
• Speed = set based on the requirements of the Master
leave the SETUP OC PARAMETERS UNCHANGED (MST/SLV
= none).
For details on how to wire the network, read
"RS485 NETWORK GUIDE LINES" available in
the download area of the Daikin website.
The following functions are recognised and managed by the
FC66003946
Rev 00
Controller for units
controller as SLAVE:
CODE
The following are the available variables:
COIL STATUS (DIGITAL READING/WRITING)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
USER MANUAL
It is strictly forbidden to reproduce this manual, even partially
DESCRIPTION
01
coil status reading
02
input status reading
03
holding register reading
04
input register reading
15
multiple coil status writing
16
multiple holding register writing
DESCRIPTION
ON/OFF controller
SUMMER/WINTER controller
ECONOMY controller
ENABLE ANTI-FREEZE controller
ENABLE ELECTRICAL HEATER controller
modulating ventilation MAN/AUTO controller
enable ON/OFF from MASTER
enable ECONOMY from MASTER
enable SUMMER/WINTER from MASTER
enable ANTI-FREEZE from MASTER
enable ELECTRIC HEATERS from MASTER
enable SETPOINT from MASTER
enable SETPOINT LIMITS from MASTER
enable VENTILATION SPEED from MASTER
KEYBOARD LOCK controller
enable HUMIDITY CONTROL consent from MASTER
enable HUMIDITY CONTROL
control for CONFIGURABLE DIGITAL OUTPUT NO.7
EN
16