SETUP parameters as follows:
• MST/SLV = set "Master" on the I/O board acting as
the MASTER of the network and "Slave" on all of the
SLAVEs in the network.
• Serial address = set a value between 2 and 34 on the
SLAVE controllers.
It is now possible to connect all of the I/O boards to the
network.
Once the board has been set as SLAVE, it can
no longer communicate with any random user
unit. Accordingly, if the settings are changed, it
will be necessary to RESET it in the following
manner: disconnect the board from the
network and, keeping it powered, place digital
input 10 in short circuit for 15 seconds (clamps
I10 and IC).
All of the hydronic units (i.e. both MASTER
and SLAVE) connected to the network must be
configured in the same way.
MIXED NETWORK
The SMALL network on CONVEYED WAVES can also be
connected to a supervision network (External Supervisor
System or SMALL solution) on RS485 through RS485 serial
port of the MASTER controller, thus obtaining what is known
as a MIXED NETWORK. Figure 04 illustrates the diagram
of a mixed network comprised of a SMALL network on
CONVEYED WAVES combined with a supervision network.
PARAMETER OUTLINING TABLE
EXTERNAL
SUPERVISOR
SMALL
SYSTEM
RS485
BMS
RS485
FWECSA
Master:
Master
Slave from
MST/SLV
SPV
FWECSA
Slave: Slave
from SPV
Protocol
Modbus
Modbus
EN
19
Controller for units
Serial Address
Speed
OC
MST/SLV
Serial Address
MEANINGS OF THE LEDS
STATUS
NETWORK
SMALL
Mixed
OC
Network
FWECSA
Master:
Master
-
FWECSA
Slave: Slave
from SPV
-
Modbus
OPERATION MANUAL
It is strictly forbidden to reproduce this manual, even partially
FWECSA
Master: 0
1... 255
FWECSA
Slave: 1...
255
Based on the
9600
Master
-
-
-
-
BLUE
GREEN
Unit OFF
Unit ON
LED
Communication
OC Master
LED
Looking at the I/O board from the front, the
STATUS LED is on the left, while the NETWORK
LED is on the right.
FWECSA
FWECSA
Master: 0
-
FWECSA
Slave: 1...
255
-
9600
FWECSA Master: Master
FWECSA Slave: Slave
FWECSA Master: 0
FWECSA Slave: 2... 255
RED
Alarm in
progress
No
OK
communication
FC66003946
Rev 00