FWECSA
I/O TABLE FOR THE BOARD
POWER SUPPLY
L
Phase
N
Neutral
INPUTS
I1
Room air NTC probe
I2
Water NTC probe
I3
Hot water NTC probe (with 4-pipe units)
I4
Not used
I5
Not used
IC
Common for NTC probes
+5
Not used
I6
Input for remote ON/OFF
I7
Input for remote SUM/WIN
I8
Input for remote ECONOMY
I9
Not used
I10
Not used
IC
Common for I6-I7-I8
SU - SU
Humidity probe
OUTPUTS
A1
Brushless fan modulation
Water valve modulation
A2
(cold with 4-pipe units)
A3
Hot water valve modulation (only with 4-pipe units)
CA
Common for 0-10V outputs
O1
Extra-low speed
O2
Low Speed
O3
Medium Speed
O4
High Speed
O5
Water valve (cold with 4-pipe units)
O6
Hot water valve (only with 4-pipe units) or heater
C1
Common for O1-O6 relay outputs
O7
Configurable signal output
C7
Common for O7 relay output
PORTS (FRONT OF BOARD)
A/B/GND
RS485 serial MODBUS protocol
+ / -
Display connection or second board
+ / -
Display connection or second board
FC66003946
Rev 00
Controller for units
ELECTRICAL DIAGRAM
(figure 19)
USER MANUAL
It is strictly forbidden to reproduce this manual, even partially
KEY
SA
Room temperature probe
SW
Water temperature probe (cold with 4-pipe units)
Hot water temperature probe (only with 4-pipe
SWH
units)
SU
Ambient humidity probe
ON/OFF
Dry contact for remote ON/OFF
SUM/WIN
Dry contact for remote SUMMER/WINTER
ECONOMY
Dry contact for remote ECONOMY
FAN 0/10V
Modulating fan 0/10V
Modulating 0/10V water valve (cold with 4-pipe
VH 0/10V
units)
VH 0/10V
Modulating hot water valve (only with 4-pipe units)
MV
Fan
INV
Fan inverter
MV INV
Inverter fan motor
V1
Extra-low speed
V2
Low speed
V3
Medium speed
V4
Maximum speed
COM
Common for ON/OFF outputs
VC
Water valve (cold with 4-pipe units)
Cold water valve (only with 4-pipe units) or electric
VH/RE
heater
CN
Unit terminal board
IL
Line switch (not included)
F
Fuse (not included)
L
Phase
N
Neutral
(figure 19)
EN