7. ELECTRICAL

All­external­wiring­must­be­in­accordance­with­the­
existing­electrical­code.­Use­wiring­diagram­furnished­
with­heater.­Be­sure­electric­supply­characteristics­
match­those­called­for­on­the­name­plate.­The­unit­
must be electrically grounded in accordance with the
National­Electrical­Code,­ANSI/NFPA70,­latest­revision.­
In­Canada­refer­to­Canadian­electrical­code­CSA­C22.1
8. THERMOSTAT & LOCATION
Make­sure­that­the­electrical­characteristics­of­the­
thermostat­match­those­of­the­heater­controls.­For­best­
results­thermostat­should­be­positioned­5­ft.­above­
floor­where­air­can­circulate­freely­around­it.­DO­NOT­
MOUNT­directly­to­cold-side­wall,­in­direct­drafts­or­
directly­beneath­the­infra-red­heater.

9. VENTILATION

a.­The­minimum­intake­and­exhaust­air­openings­shall­
provide­for­not­less­than­400­CFM­for­every­100,000­
BTU­input­except­that­the­infiltration­area­may­be­
included­in­the­intake­area.­The­exhaust­fan­must­be­
interlocked­with­the­heater­thermostat.­If­a­power­
exhaust­fan­is­used,­it­should­be­controlled­by­the­
thermostat or humidistat
b.­Where­natural­ventilation (gravity)­is­provided­for­
exhaust,­the­openings­must­be­distributed­above­
the­heaters­(preferably­at­the­peak­of­the­roof)­and­
the­areas­of­openings­shall­not­be­less­than­300­
square­inches­for­every­100,000­BTU­input.

10. OPERATIONS

Upon­completion­of­electrical­wiring,­gas­piping­and­
purging of gas lines to heaters, refer to the lighting
instruction plate attached to heater for proper lighting
procedure.
FIGURE 2
BTU/HR.­RATING
MODEL
GAS
NO.
NATURAL
PROPANE­ ­
4030
30,000
30,000
4040
40,000
40,000
8050
50,000
50,000
8060
60,000
60,000
8070
70,000
9080
80,000
80,000
9090
90,000
90,000
9100S
100,000
100,000
9100
100,000
100,000
9120
120,000
120,000
9140
140,000
Enerco Group, Inc. | Gas-Fired Infra-Red Space Heaters
GAS­SUPPLY­PRESSURE­(W.C.)
MIN.
NAT.
L.P.
6.6"
11"
6.8"
11"
7.0"
11"
7.0"
11"
7.0"
7.0"
11"
7.0"
11"
7.0"
11"
7.0"
11"
7.0"
11"
7.0"

11. CLEANING INFORMATION

Blow­out­Venturi­and­burner­face­with­compressed­air­
(25psi­max.­pressure);­also­clean­orifices­(see­Figure­
2­for­correct­size­drill).­For­detailed­maintenance­and­
cleaning­instructions­contact­your­local­representative­
or factory.
WARNING:
GASKET­BINDER­MATERIAL­USED­
IN­THIS­HEATER­ASSEMBLY­WILL­TEMPORARILY­
EMIT­AN­ODOR­AND/OR­VAPOR.­USE­VENTILATION­
(a­OR­b)­AND­THIS­CONDITION­WILL­CLEAR­UP­
IN­APPROXIMATELY­20­MINUTES­AND­WILL­NOT­
REOCCUR.
WARNING:
DO­NOT­ATTEMPT­TO­IGNITE­
THE­PILOT­BY­HAND­ON­HEATERS­EQUIPPED­WITH­
AUTOMATIC­SPARK­IGNITION.
WARNING:
THE­STATE­OF­CALIFORNIA­REQUIRES­
THE­FOLLOWING­WARNING:­COMBUSTION­BY-
PRODUCTS­PRODUCED­WHEN­USING­THIS­PRODUCT­
CONTAIN­CARBON­MONOXIDE,­A­CHEMICAL­KNOWN­
TO­THE­STATE­OF­CALIFORNIA­TO­CAUSE­CANCER­
AND­BIRTH­DEFECTS­(OR­OTHER­REPRODUCTIVE­
HARM).
NOTE:
USE­LATEST­EDITION­FOR­ALL­ANSI­
STANDARD­AND­CANADIAN­STANDARDS.
MAX.
MANIFOLD
NAT.
L.P.
NAT.
14"
14"
5.6"
14"
14"
5.8"
14"
14"
4.3"
14"
14"
5.8"
14"
6.0"
14"
14"
5.8"
14"
14"
5.0"
14"
14"
5.0"
14"
14"
4.3"
14"
14"
5.8"
14"
5.5"
E5
Operating Instructions and Owner's Manual
ORIFICE­SIZE
L.P.
NAT.
L.P.
10"
43
52
10"
37
49
10"
30
45
30
10"
43
29
10"
37
49
10"
32
47
10"
31
46
10"
30
45
30
10"
43
29

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido