Panasonic U-20GES3E5 Manual Del Usuario página 9

Ocultar thumbs Ver también para U-20GES3E5:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 141
Table 1-5 Branch/Header Tube Selection
Use the following branch tubing sets or tubing sets for branching the system's main tube and indoor unit
tubing.
Capacity after branch
Gas tube (mm)
Over 72.8 kW
Over 45.0 kW to 72.8 kW
Over 35.5 kW to 45.0 kW
Over 28.0 kW to 35.5 kW
Over 16.0 kW to 28.0 kW
Over 5.6 kW to 16.0 kW
5.6 kW or below
(*1)
Make a selection so as not to exceed the main tubing size.
(*2)
Even when 5.6 kW or below, make the gas tube diameter Ø15.88 if 2 or more indoor units are connected after
branching.
(*3)
As the tube diameter for the supplied reducer does not match, another reducer must be provided by the installer.
Table 1-6 Tubes Connecting Outdoor Units and Indoor Units
Outdoor Units
Tubing connecting to
outdoor units (L5)
Tube size
Indoor Units
Tubing
connecting to
Unit type
indoor units
(ℓA to ℓB)
Gas tube (mm)
Tube size
Liquid tube (mm)
Note: Keep the maximum length between ℓ1 to ℓn within 30 m.
1. LM: Main tube with largest tubing diameter (includes LA and all post-branch main tubes that are identical in size to LA) ≤ 120 m.
2. Select the sizes for post-branching main tubes after LM (LB, LC, ...) based on the post-branching capacity.
3. The sizes for the indoor unit connection tubing (ℓ1 to ℓn) depend on the tubing diameter for the indoor unit.
H3
Lb
L5
L5
Balance tube
No.1 branch
Symbols
Branch tube
(purchased separately)
L4
Ball valve
(purchased separately)
T-tee
(provided by installer)
Closed (pinch) weld
Maximum height differential of indoor units after final branch
Four meters is the maximum height differential between
indoor units after the last branch.
Branch tube size
(*1)
Liquid tube (mm)
Ø31.75
Ø19.05
Ø28.58
Ø15.88
Ø28.58
Ø12.7
Ø25.4
Ø12.7
Ø22.22
Ø9.52
Ø15.88
Ø9.52
Ø12.7
Ø9.52
(*2)
Unit type
Gas tube (mm)
Liquid tube (mm)
22
28
36
45
Ø12.7
Ø6.35
LM
LB
LC
LA
4
LF
40 cm or less
Used for expansion
40 cm or less
1
LG
4 m or less
(within α)
Fig. 5 Length of Refrigerant Tubing
EN - 9
Branch tube number
Branch tubing
CZ-P160BK2
CZ-P680PJ(BK)2
U-10MES2E8
Ø22.22
Ø9.52
56
60
73
90
106
140
Ø15.88
L2
When T-tee branch tubing is
used (header branch method)
LD
LE
L3
5
6
7
LH
2
3
If exceeding the 4 m of height between indoor units after a
final branch cannot be helped, split the difference between
rise and fall (2:1).
2X m or
more
X m
CZ-P1350PJ(BK)2
(*3)
(*3)
(*3)
(*3)
U-20GES3E5
Ø28.58
Ø15.88
160
224
280
Ø19.05
Ø22.22
Ø9.52
L1
H1
n
H2
More than 4 m
(within α)

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

U-10mes2e8

Tabla de contenido