Example
Remark
38 / 120
Siemens
Building Technologies
The formulas in the table above provide approximated values for
controller settings. Therefore additional fine-tuning is highly recom-
mended.
Liquid cooler (shell-and-tube heat exchanger)
Parameter code
ΔT XP
ΔT TN
MOP XP
MOP TN
The MOP function can be set up using the parameters. Normally, the
factory settings should not be changed.
Superheat - CPS40
Commissioning
old
new
30 K
30 K * 1,25 = 38 K
65 s
65 s
20 k
50 K / 20K = 2,5 > 0,75
à 50 K / 0,75 = 67 K or higher
40 s
40 s
CE1U3372xx
2018-11-09