Certification - Federal Signal Global Serie Instrucciones De Instalación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation and Maintenance Instructions
Keep the unit tightly closed when in operation.
After testing is complete, provide a copy of this instruction sheet
to all personnel.
Establish a procedure to routinely check the loudspeaker system
for proper activation and operation.
Failure to follow all safety precautions and instructions may result in
property damage, serious injury, or death.

Certification

Certificate Nos.: ATEX Cert No.: Baseefa15ATEX0155X
Protection:
Standards:
Specific Conditions of Use:
1.
The Modular Audible Device enclosure incorporates a sinter and
the volume is greater than 100 cm
Audible Device in carbon disulphide gas atmospheres is not
permitted.
2.
The Modular Audible Device has external non-metallic surfaces
which may provide electrostatic charging hazard. See the
manufacturer's instructions for further information.
3.
The Modular Audible Device has metallic components in the non-
metallic walls of the enclosure which can store electrical charge
and therefore may provide a potential electrostatic discharge.
The metallic brass inserts have a capacitance of 24 pF. See the
manufacturer's instructions for further information.
6
IECEx Cert No.: IECEx BAS 15.0104X
ATEX coding:
Ex db IIB T5 Gb or Ex db e IIB T5 Gb
Ex tb IIIC T100°C Db IP66
Ex db IIC T4 Gb or Ex db e IIC T4 Gb
Ex tb IIIC T135°C Db IP66
EN60079-0: 2012 +A11:2013, EN60079-1: 2014,
EN60079-7: 2007, EN60079-31: 2014, IEC60079-0: 7th Ed.,
IEC 60079-1:6th Ed., IEC 60079-7: 4th Ed.,
IEC 60079-31:2nd Ed.
Model G-SPK Global Series Loudspeaker
II 2 G D
(Tamb = -50°C to + 49°C)
(Tamb = -50°C to + 60°C)
, therefore use of the Modular
3

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

G-spk

Tabla de contenido