Descargar Imprimir esta página

Ecoflam Multiflam 500.1 Manual Del Usuario página 35

Quemadores mixtos gas / fuel pesado

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 62
420010309700 Multiflam 500.1 - 600.1 PR/PR
EN
ADJUSTMENT OF FUEL TEMPERATURE
Display
Decrease key
Increase key
"Function" key
The display shows oil temperature.
The 4 leds are related to the following functions:
Out 1: contact driving working heaters. Out 2: contact driving upper heaters KMRL1. Out 3: contact driving
upper heaters KMRL2. Out 4: Burner start driving contact (as the oil reaches this temp the pump is activated).
- The temperatures are already properly Factory setted :Out 1(113°)- Out 2(115°)- Out 3(120°)- Out 4(105°).
- To modify factory temperature setting act as follows:
- press key "F"
- the led Out1 starts to flash, if You need to modify minimum oil temperature press increase or decrease but-
ton, after confirm the new value pressing again "F"
- if You need to modify an other temperature press again "F" untill You the relevant led flashes.
Please take care: if key "F" is pressed for a too long time, You enter in "configuration level" phase1, (see "CF1"
on the display); these parameters are Factory setted and they have not to be modified: if You enter this function
– You see CF1 flashing on the display – wait 10 seconds untill the regulator automatically goes out from "confi-
guration level".
35

Publicidad

loading

Este manual también es adecuado para:

Multiflam 600.1Multiflam 500.1 pr/prMultiflam 600.1 pr/pr