Digital Input - Emerson dixell XW60K E T620T Instrucciones De Manejo

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

dIXEL
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off
in case of faulty thermostat probe. With COF=0 compressor is always active.
DISPLAY
CF Temperature measurement unit: °C = Celsius; °F = Fahrenheit . When the measurement unit
is changed the SET point and the values of the regulation parameters have to be modified
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display.
dE = 0,1°C
in = 1 °C
rEd Remote display : select which probe is displayed by the remote display ( T620or CX620 or
V620)
(P1; P2, P3, P4, SET, dtr): it selects which probe is displayed by the instrument: P1 =
Thermostat probe; P2 = Evaporator probe; P3 = Third probe(only for model with this option
enabled); P4 = Fourth probe, SET = set point; ; dtr = percentage of visualization.
dLy Display delay: (0 ÷20.0m; risul. 10s) when the temperature increases, the display is updated of
1 °C/1°F after this time.
dtr Percentage of the second and first probe for visualization when Lod = dtr (0÷100; 100 =
P1, 0 = P2 ): if Lod = dtr it allows to set the visualization according to the percentage of the first
and second probe, as for the following formula (dtr(P1-P2)/100 + P2).
DEFROST
tdF Defrost type:
EL = electrical heater (Compressor OFF)
in = hot gas (Compressor and defrost relays ON)
dFP Probe selection for defrost termination: nP = no probe; P1 =thermostat probe; P2 =
evaporator probe; P3 =Third probe; P4 = Fourth probe.
dtE Defrost termination temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the
evaporator probe is present) sets the temperature measured by the evaporator probe which
causes the end of defrost.
IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two
defrost cycles.
MdF (Maximum) duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the
defrost duration, when P2P = y, defrost end based on temperature, it sets the maximum length
for defrost.
dSd Start defrost delay: ( 0÷99min) This is useful when different defrost start times are necessary to
avoid overloading the plant.
dFd Display during defrost:
rt = real temperature;
it = temperature reading at the defrost start;
Set = set point;
dEF = "dEF" label;
dEG = "dEG" label;
÷
dAd Defrost display time out: (0
255 min) Sets the maximum time between the end of defrost and
the restarting of the real room temperature display.
Fdt Drain down time: (0÷60 min.) time interval between reaching defrost termination temperature
and the restoring of the control's normal operation. This time allows the evaporator to eliminate
water drops that might have formed due to defrost.
dPo First defrost after start-up:
y = Immediately;
n = after the IdF time
dAF Defrost delay after fast freezing: (0min÷23h 50min) after a Fast Freezing cycle, the first
defrost will be delayed for this time.
FANS
FnC Fan operating mode:
C-n = running with the compressor, OFF during the defrost;
C-y = running with the compressor, ON during the defrost;
O-n = continuous mode, OFF during the defrost;
O-y = continuous mode, ON during the defrost;
Fnd Fan delay after defrost: (0÷255 min) The time interval between the defrost end and evaporator
fans start.
Fct Temperature differential avoiding short cycles of fans (0÷59°C; Fct=0 function disabled). If
the difference of temperature between the evaporator and the room probes is more than the
value of the Fct parameter, the fans are switched on.
FSt Fan stop temperature: (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator
probe, above which the fan is always OFF.
Fon Fan ON time: (0÷15 min) with Fnc = C_n or C_y, (fan activated in parallel with compressor). it
sets the evaporator fan ON cycling time when the compressor is off. With Fon =0 and FoF ≠ 0
the fan are always off, with Fon=0 and FoF =0 the fan are always off.
FoF Fan OFF time: (0÷15 min) with Fnc = C_n or C_y, (fan activated in parallel with compressor). it
sets the evaporator fan off cycling time when the compressor is off. With Fon =0 and FoF ≠ 0 the
fan are always off, with Fon=0 and FoF =0 the fan are always off.
FAP Probe selection for fan management: nP = no probe; P1 =thermostat probe; P2 = evaporator
probe; P3 =configurable probe; P4 = Probe on Hot Key plug.
OA3 = AUS: AUXILIARY THERMOSTAT CONFIGURATION (terms. 22-23)
ACH Kind of regulation for auxiliary relay: Ht = heating; CL = cooling
SAA Set Point for auxiliary relay: (-50,0÷110,0°C; -58÷230°F) it defines the room temperature
setpoint to switch auxiliary relay.
SHy Differential for auxiliary relay: (0,1÷25,5°C; 1÷45°F): Intervention differential for auxiliary relay
set point, always positive.
ArP Probe selection for auxiliary: nP = aux relay is switched by digital input with i1F = AUS; P1 =
Probe 1 (Thermostat probe); P2 = Probe 2 (evaporator probe); P3 = Probe 3 (display probe).; P4
= Probe 4
Sdd Auxiliary output working during defrost:
n = the auxiliary output is switched off during defrost
y = the auxiliary output goes on working during defrost
ALARMS
ALP Probe for temperature alarm setting: P1 = thermostat probe; P2 = evaporator probe; P3 =
condenser 1 probe; P4 O condenser 2 probe.
ALC Temperature alarm configuration
rE = High and Low alarms related to Set Point
Ab = High and low alarms related to the absolute temperature.
ALU High temperature alarm setting:
÷
ALC= rE, 0
50°C or 90°F
÷
ALC= Ab, ALL
110°C or 230°F
when this temperature is reached and after the ALd delay time the HA alarm is enabled.
1592026020 XW60K GB R1.0 22.02.2008.doc
Installing and Operating Instructions
ALL Low temperature alarm setting: ALC = rE , 0
÷
or -58°F
ALU when this temperature is reached and after the ALd delay time, the LA alarm is
enabled.
AFH Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for
temperature alarm set point and fan regulation set point, always positive.
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm
condition and the corresponding alarm signalling.
dAo Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection
of the temperature alarm condition after the instrument power on and the alarm signalling.
CONDENSER TEMPERATURE ALARM
AP2 Probe selection for temperature alarm of condenser: nP = no probe; P1 =thermostat probe;
P2 = evaporator probe; P3 =third probe; P4 = fourth probe.
AL2 Low temperature alarm of condenser: (-55÷150°C) when this temperature is reached the LA2
alarm is signalled, possibly after the Ad2 delay.
Au2 High temperature alarm of condenser: (-55÷150°C) when this temperature is reached the HA2
alarm is signalled, possibly after the Ad2 delay.
AH2 Differential for temperature condenser alarm recovery: (0,1÷25,5°C; 1÷45°F)
Ad2 Condenser temperature alarm delay: (0÷255 min) time interval between the detection of the
condenser alarm condition and alarm signalling.
dA2 Condenser temperature alarm exclusion at start up: (from 0.0 min to 23.5h, res. 10min)
bLL Compressor off with low temperature alarm of condenser: n = no: compressor keeps on
working; Y = yes, compressor is switched off till the alarm is present, in any case regulation
restarts after AC time at minimum.
AC2 Compressor off with high temperature alarm of condenser: n = no: compressor keeps on
working; Y = yes, compressor is switched off till the alarm is present, in any case regulation
restarts after AC time at minimum.
RELAY OA3 (22-23) CONFIGURATION
tbA Alarm relay silencing (with oA3=ALr):
n= silencing disabled: alarm relay stays on till alarm condition lasts,
y =silencing enabled: alarm relay is switched OFF by pressing a key during an alarm
oA3 Fourth relay configuration (22-23): dEF: do not select it!.; FAn: do not select it!.; ALr: alarm;
Lig: light; AuS: Auxiliary relay; onF: always on with instrument on; db = heating element for
neutral zone regulation; cP2 = second compressor, dF2: do not select it.
AoP Alarm relay polarity: it set if the alarm relay is open or closed when an alarm happens. CL=
terminals 1-2 closed during an alarm; oP = terminals 1-2 open during an alarm

DIGITAL INPUT

i1P Digital input polarity: oP: the digital input is activated by opening the contact; CL: the digital
input is activated by closing the contact.
i1F Digital input configuration: EAL = external alarm: "EA" message is displayed; bAL = serious
alarm "CA" message is displayed. PAL = pressure switch alarm, "CA" message is displayed; dor
= door switch function; dEF = activation of a defrost cycle; AUS =to switch on and off the 22-23
relay with oA3 = AUS; Htr = kind of action inversion (cooling – heating); FAn = not set it; ES =
Energy saving.
did: (0÷255 min) with i1F= EAL or i1F = bAL digital input alarm delay: delay between the detection
of the external alarm condition and its signalling.
with i1F= dor: door open signalling delay
with i1F = PAL: time for pressure switch function: time interval to calculate the number of the
pressure switch activation.
÷
nPS Pressure switch number: (0
15) Number of activation of the pressure switch, during the "did"
interval, before signalling the alarm event (I2F= PAL).
If the nPS activation in the did time is reached, switch off and on the instrument to restart
normal regulation.
odc Compressor and fan status when open door: no = normal; Fan = Fan OFF; CPr =
Compressor OFF; F_C = Compressor and fan OFF.
rrd Outputs restart after doA alarm: no = outputs not affected by the doA alarm; yES = outputs
restart with the doA alarm;
HES Temperature increase during the Energy Saving cycle : (-30,0°C
the increasing value of the set point during the Energy Saving cycle.
OTHER
Adr RS485 serial address (1÷247): Identifies the instrument address when connected to a ModBUS
compatible monitoring system.
PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC probe, ntc =
NTC probe.
onF on/off key enabling: nu = disabled; oFF = enabled; ES = to start a energy saving cycle.
dP1 Thermostat probe display
dP2 Evaporator probe display
dP3 Third probe display- optional.
dP4 Fourth probe display.
rSE Real set point: it shows the set point used during the energy saving cycle or during the
continuous cycle.
rEL Release software: (read only) Software version of the microprocessor.
Ptb Parameter table: (read only) it shows the original code of the dIXEL parameter map.
7. Digital input
The free voltage digital input is programmable in different configurations by the "i1F" parameter.
DOOR SWITCH INPUT (i1F = dor)
It signals the door status and the corresponding relay output status through the "odc" parameter: no =
normal (any change); Fan = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter "did", the door alarm is enabled,
the display shows the message "dA" and the regulation restarts is rtr = yES. The alarm stops as
soon as the external digital input is disabled again. With the door open, the high and low temperature
alarms are disabled.
GENERIC ALARM (i1F = EAL)
As soon as the digital input is activated the unit will wait for "did" time delay before signalling the "EAL"
alarm message. The outputs status don't change. The alarm stops just after the digital input is de-
activated.
XW60K
1592026020
÷
50 °C or 90°F;
ALC = Ab , - 50°C
÷
30,0°C/-22÷86°F) it sets
3/5

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Dixell xw60k e t629Dixell xw60k e v620Dixell xw60k e cx620

Tabla de contenido