Basic Installation
To Fixture
From Cold Supply
To Model
L111, LFL111, MMV or LFMMV
† N170-M3
or LFN170-M3
Tempering
Valve
Shutoff Valves
(on both hot
and cold inlets)
Check Valves
(on both hot and
cold inlets)
Minimum Flow Requirements to
Maintain Set Temperature
for N170-M3 or LFN170-M3 Series
Valve Size
⁄
" thru 2" (20-50mm) 3 to 7 (11 to 26.5 lpm)
3
4
Specifications
• Maximum Operating Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 psig (861 kPa)
• Maximum Hot Water Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 200°F (93°C)
• Minimum Hot Water Supply Temperature . . . . . . . . . . . . . . . . . . . . . 5°F (3°C) Above Set-Point*
• Temperature Adjustment Range** . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 - 180°F (32 - 82°C)
• Hot Water Inlet Temperature Range . . . . . . . . . . . . . . . . . . . . . . . . . 120 - 180°F (42 - 82°C)
• Cold Water Inlet Temperature Range . . . . . . . . . . . . . . . . . . . . . . . . 40 - 80°F (4 - 27°C)
• Listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASSE 1017, IAPMO
• Approval Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASSE 1017, CSA B125.3
* With Equal Pressure
** Low limit can not be less than the cold water temperature. For best operation, hot water should be at least 5°F (3°C)
above desire set point.
2
ATTENTION INSTALLER: After installation,
Thermometer
Tempered 140°F *†
8" to 12"
180°F
Storage
Tank
Drain
gpm
please leave this Instruction Sheet for
occupant's information.
Cold
CSA/ASME T&P Valve
ASME Pressure
Relief Valve
Water Heater
or
Hot Water Boiler
Hot
Water
NOTE: Heat trap is recommended.
† Valves listed to ASSE Standard 1016, 1069
or 1070, such as the Watts L111, LFL111,
USG, LFUSG, MMV, or LFMMV should be
used at point of delivery.
UPC
C
Temperature
Adjusting Screw
Lock Nut
Actuator
Cold
Water