Minebea Intec PR6130/65S Manual De Instalación página 43

Caja de conexiones de cable
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Canadian Certificate Of Conformity No: FM17CA0156X
10.
Equipment Ratings:
Intrinsically safe for Class I, II and III, Division 1, Groups A, B, C, D, E, F and G hazardous locations;
Intrinsically safe for Class I, Zone 0, Group IIC hazardous (classified) locations; Nonincendive for Class I,
Division 2, Groups A, B, C, and D, hazardous locations; Suitable for Class II and III, Division 2 hazardous
locations. Temperature classification T4.
Intrinsically safe for Zone 20, Group IIIC hazardous locations Temperature classification T90°C.
Ambient temperature range -20°C to +60°C for PR 6130/6ab and PR 6021/68S,-30°C to +60°C for
PR6130/64Sa-Temp, PR6130/64C-Temp and PR6130/65S-Temp and -40°C to 60°C for PR6130/68S-
Temp and PR6021/68S-Temp. Indoor and outdoor Type 4X and IP6x.
11.
The marking of the equipment shall include:
PR 6130/6[a][b] and PR 6021/68S Cable Junction Box
IS CL I, II, III, DIV 1, GP A,B,C,D,E,F,G T4 - 36931-751-07; Type 4X, IP6x
NI CL I, DIV 2, GP A,B,C,D, T4; Type 4X, IP6x
DIP CL II, DIV 2, GP E,F,G T4; Type 4X, IP6x
CL I, Zone 0, Ex ia IIC T4 - 36931-751-07; Type 4X, IP6x
Zone 20, Ex ia IIIC T90°C - 36931-751-07 Tyoe 4X, IP6x
Ta= -20°C to 60°C
PR 6130/64Sa-Temp, PR 6130/64C-Temp and PR 6130/65S-Temp Cable Junction Box
IS CL I, II, III, DIV 1, GP A,B,C,D,E,F,G T4 - 36931-731-07; Type 4X, IP6x
NI CL I, DIV 2, GP A,B,C,D, T4; Type 4X, IP6x
DIP CL II, DIV 2, GP E,F,G T4; Type 4X, IP6x
CL I, Zone 0, Ex ia IIC T4 - 36931-731-07; Type 4X, IP6x
Zone 20, Ex ia IIIC T90°C - 36931-751-07 IP6x
Ta= -30°C to 60°C
PR 6130/68S-Temp and PR 6021/68S-Temp Cable Junction Box
IS CL I, II, III, DIV 1, GP A,B,C,D,E,F,G T4 - 36931-721-07; 4X, IP6x
NI CL I, DIV 2, GP A,B,C,D, T4; 4X, IP6x
DIP CL II, DIV 2, GP,E,F,G T4; 4X, IP6x
CL I, Zone 0, Ex ia IIC T4 - 36931-721-07; 4X, IP6x
Zone 20, Ex ia IIIC T90°C - 36931-751-07 Type 4X, IP6x
Ta= -40°C to 60°C
12.
Description of Equipment:
General - The Cable Junction Boxes are designed to interconnect up to 8 load cells and then connect this
arrangement to the interface of an evaluation unit (e.g. indicator).
Construction - The Cable Junction Boxes series PR 6130/6... and PR 6021/6... consist of stainless steel
housings with ingress protection IP6x in accordance with ANSI/IEC 60529 and Type 4X. All screws, flat and
lock washers are also made of stainless steel.
Ratings
Operation Temperature Ranges:
The ambient operating temperature range of the Cable Juction Boxes PR 6130/6ab and PR 6021/68S is up
to -20°C to +60°C.
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail:
F 348 (Mar 16)
SCHEDULE
information@fmapprovals.com www.fmapprovals.com