Battery Charging Information - Victron energy BlueSolar MPPT 100/30 Manual

Ocultar thumbs Ver también para BlueSolar MPPT 100/30:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

3.7 Battery charging information

The charge controller starts a new charge cycle every moring,
when the sun starts shining.
The maximum duration of the absorption period is determined by
the battery voltage measured just before the solar charger starts
up in the morning:
Battery voltage Vb (@start-up)
Vb < 23,8V
23,8V < Vb < 24,4V
24,4V < Vb < 25,2V
Vb > 25,2V
(divide voltages by 2 for a 12 V system)
If the absorption period is interrupted due to a cloud or due to a
power hungry load, the absorption process will resume when
absorption voltage is reached again later on the day, until the
absorption period has been completed.
The absorption period also ends when the output current of the
solar charger drops to less than 2 Amps, not because of low solar
array output but because the battery is fully charged (tail current
cut off).
This algorithm prevents over charge of the battery due to daily
absorption charging when the system operates without load or
with a small load.
8
Maximum absorption time
6 h
4 h
2 h
1 h

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Bluesolar mppt 100Bluesolar mppt 300Blue power bluesolar mppt 100/30

Tabla de contenido