Connecting the FCS-320-TP/-TT series
See Figure 4, Page 5:
Terminal Terminal block X7
1
2
3
4
5
6
7
8
9
Parameter Settings Using the DIP Switch
The aspirating smoke detector parameters are set using the DIP switch on the detector
modules. The default settings are marked in bold in each case. Select all other parameters
(see tables).
Sensitivity
DM-TP-01(05)
DM-TT-01(05)
0,12 %/m(0,4 %/m) 0,8 %/m(2 %/m)
0,06 %/m(0,2 %/m) 0,4 %/m(1 %/m)
0,03 %/m(0,1 %/m) 0,2 %/m(0,5 %/m)
0,015 %/m(0,05 %/
m)
Alarm delay
0 seconds
10 seconds
30 seconds
60 seconds
Activation threshold for airflow malfunction
Low (+/- 10% volume flow change)
Average (+/- 20% volume flow change)
High (+/- 30% volume flow change)
Very high (+/- 50% volume flow change)
Airflow fault delay
30 seconds
2 minutes
15 minutes
60 minutes
Trouble logging
not saving
saving
NOTICE!
The sensitivity value is based on measurements with standard test fires (old value in
brackets).
The activation threshold for the airflow malfunction is set to 20% volume flow change by
default. Higher values are not permitted within EN 54-20.
Commissioning
See Figure 5, Page 5:
Bosch Sicherheitssysteme GmbH
Fault 2
Fault contact for 2nd detector module
Al 2
NO contact for 2nd alarm relay
C contact for 2nd alarm relay
NC contact for 2nd alarm relay
+ Ext. Displ.2
Remote indicator for 2nd detector module
- Ext. Displ.2
Fault 1
Fault contact for 1st detector module
DM-TP10(25)
DM-TT-10(25)
0,1 %/m(0,25 %/m) 0,5 %/m(0,8 %/m)
DIP settings
Switch 9
off
on
DIP settings
DM-TP50(80)
Switch 1
DM-TT-50(80)
1,0 %/m(1,6 %/m)
DIP settings
Switch 3
off
on
off
on
DIP settings
Switch 5
on
off
off
on
DIP settings
Switch 7
off
on
on
off
LOGIC·SENS filter
off
on
en
27
Switch 2
on
on
off
on
on
off
off
off
Switch 4
off
off
on
on
Switch 6
off
on
off
on
Switch 8
on
off
on
off
DIP settings
Switch 10
off
on
F.01U.130.927 | 2.0 | 2010.12