Lamborghini Caloreclima 310 PM/M-E Manual Para La Instalación Y El Mantenimiento página 49

Ocultar thumbs Ver también para 310 PM/M-E:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

PRESSURE SWITCH TYPE: GW 150 A5
CALIBRATION OF AIR PRESSURE SWITCH
The air pressure switch places the burner in safety mode or shuts it down should there be a drop in combustion
air pressure. It will be calibrated at a pressure below 1st stage rated-flow on-burner air pressure, checking
that CO values do not exceed 10,000 p.p.m..
CALIBRATION OF MINIMUM GAS PRESSURE SWITCH
The minimum gas pressure switch serves to prevent the burner from being started up or to shut it down if the
gas pressure falls below the minimum required level. This setting should be 40% lower than the gas pressure
obtained with the burner operating at maximum delivery.
PRESSURE
Type:
LGW 10 A2
GW 150 A5
Remove the cover and adjust
dial (A)
Model
310 PM/M - E
430 PM/M - E
CHECKING IONIZATION CURRENT
The minimum value of 30 μA should be observed,
and large oscillations are to be avoided.
Microamperemeter connection
GAS PRESSURE
Pressure
outlet
Air pressure
switch type
DUNGS LGW 10 A2P
DUNGS LGW 10 A2P
Setting range
mbars
1 - 10
DUNGS GW 150 A5
1 - 10
DUNGS GW 150 A5
AIR PRESSURE
Air pressure
switch type
49
Setting range
mbars
5 - 120
5 - 120

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

430 pm/m-e

Tabla de contenido