10.2 HEAT EXCHANGER

Using a screwdriver, remove the four screws of the heat exchanger inspection panel bolts.
Rotate the four securing bolts until the panel is free and can be removed.
Using a star screwdriver, release the bolts securing the safety bar located in the angle of the heat exchanger.

10.3. DRAINPIPE FOR CONDENSATE

Regularly inspect the drainpipe for condensates to make sure it is not blocked, if this is the case, remove the obstruction.

11. OPERATION ANOMALIES

ANOMALY
Difficult to start.
Reduced power supply voltage.
Insufficient static torque of motor.
Insufficient airflow.
Blocked pipes and/or inlet points closed.
Insufficient pressure.
Fan obstructed.
Filter overloaded.
Insufficient rotation speed.
Exchanger package blocked.
Reduction in performance
Leaks in the circuit before and/or after
after a period of acceptable
the fan.
operation.
Damaged roller.
New air temperature too
Outside air -5º C or less.
cold.
Models (CADB-DI): Thermal protectors
Support resistances open.
Insufficient performance of
Fins dirty.
the exchanger.
Formation of frost on the
Outside air below -5º C.
exchanger.
Air pulsation.
Fan working in flow conditions almost 0.
Flow instability, obstruction or bad
connection.
ATTENTION! Hold the exchanger with one hand during this operation to avoid it falling (risk of damaging
the exchanger and risk of accident for the technician carrying out the operation).
To remove the exchanger from its location, slide it along its guides, pulling by the handle and not the
exchanger fins, so as not to damage the exchanger.
Clean the exchanger with compressed air or with a vacuum cleaner and wash it with a mild detergent.
The recommended regular maintenance should be carried out once per season when it is in operation.
CAUSE
26
SOLUTION
Check motor specification plate.
Close the air inlets to reach the maximum speed.
Change the motor is necessary.
Contact the S&P Post-Sales service.
Clean inlet tubes.
Clean fan.
Clean or replace filter.
Check power supply voltage.
Clean the exchanger.
Check the circuit and restore original conditions.
Check the impeller and if necessary, replace with an original spare part.
Contact the S&P post sales service.
Insertion of post-heating resistances.
Contact the S&P post sales service.
Reset by pushing the button RESET, all the thermal protectors of the
resistance.
Clean the exchanger.
Insertion of post-heating devices (anti-ice).
Contact the S&P Customer Advice service.
Modification of the circuit and/or replacement of the fan.
Clean and/or readjust the inlet channels. Operate the electronic regula-
tor, increasing the minimum speed (insufficient voltage).
Contact the S&P Customer Advice service.