Installation of the limit indicator to the tank
• Prior to installation into the tank, re-check the adjusting dimension X and control dimension
Y for correctness.
• The installation location for the limit indicator regarding battery tanks according to DIN 6620
is shown in table 1 in figure 1a and figure 1b.
• Regarding tanks pursuant to DIN 6625 with internal ceiling braces, the limit indicator must
be installed in the same field as the ventilation line.
• Carefully insert the probe tube of the GWG through the designated tank bushing and tank
nozzle, respectively; do not damage the sensor!
• Screw-in the insert into the tank bushing using a gasket or sealing materials manually and fit
the tank panel onto the tank nozzle using a gasket, respectively.
• The gasket and the sealing material, respectively, must not be damaged during installation
so that the odour tightness and the tightness in flooding and risk areas is provided for.
• The notch as the mark for the probe length and the value for Z must be visible upon
installation.
• If required, the probe tube protruding from the tank must be protected against mechanical
loads.
Table 3: Type GWD limit indicator with type FSA level gauge

CONNECTOR

The connector is the interface between the limit indicator and the road tanker. This interface
must be mounted directly next to the filling hole plug of the filler line.
If several systems with filling hole plug and limit indicator are located nearby, it must be
ensured that the filling hole plug can be assigned unambiguously to the corresponding
connectors of the limit indicator. The connector must be attached sufficiently. It must be
possible to easily couple with the connection line of the controller of the overfill prevention
mechanism.
Part No. 15 382 57 a
Limit indicator GWG - type GWD -issue 2
• For a detailed description, see assembly and operating
manual type FSA level gauge,
Order no. 15 276 50.
• Type FSA level gauge and type GWD limit indicator are
combined in one unit or designed to be equipped with a
limit indicator.
• Set the determined adjusting dimension X, as shown
alongside.
Sondenlänge Z: probe length Z
Einstellmaß X: adjusting dimension X
Kontrollmaß Y: control dimension Y
9 / 12