Table 4:
Standard connector wall fitting – fitting for wall assembly type 905
• The wall fitting is supplied separately and must be connected to the limit indicator.
• The wall fitting must be attached sufficiently.
• The free end of the limit indicator's cable is routed perpendicularly to the ceiling or a
nearby wall.
If the filling hole plug is farther away from the tank (e.g. regarding a central filling hole), limit
indicators with cable connection fitting
connection between the cable connection fitting and the wall fitting must be provided with a
cable/line 2 x 1mm².
The maximum length may be: 150m for 2 x 1mm²,
Assembled wall fitting
If the filling hole plug is located directly adjacent to the installation location of the limit
indicator, limit indicators with assembled wall fitting must be used. For the type GWD limit
indicator, the assembled wall fitting assumes the function of the connector.
Type 904 pipe fitting as with type GWS.
Filling hole plug for limit indicator
Instead of the wall fitting, it is also possible to use a filling hole plug for limit
indicator type 906.

OPERATION

1. Using the connector, connect the limit indicator to the male contact of the overfill
prevention mechanism of the road tanker.
2. Fill the tank upon approval.
3. Upon completion of filling, fit back the cap of the connector.
10 / 12
Limit indicator GWG - type GWD -issue 2
(order no. 15 379 00) and wall fitting are used. The
250m for 2 x 1.5mm².
Part No. 15 382 57 a