4.2
General settings
4.2.1
Where to find the "Setup monitor" menu
Battery Monitor
12.1V 0.0A 100%
Battery voltage
12.10 V
Setup controller
[Press enter]
Note: If you cannot find the "Setup monitor" menu, make sure that your
VPN is set to "user and install" mode.
4.2.2
Setup parameters explained
Name
Battery capacity
Sync. voltage
Sync. current
Sync. time
Bat. temperature
Resync. to 100%?
Device name
The settings on the advanced menu allow fine control of the battery
monitoring calculations performed by the VBC.
12
Step1) Press "Enter" to enter the VBC menu.
Step 2) Press "▼" to scroll through the menu
until you see "Setup monitor".
Step 3) Press "Enter" to enter the "Setup
monitor" menu.
Setup monitor
Description
The battery capacity in amp hours (Ah) at a
20 h discharge rate.
The battery controller considers the battery as
fully charged if the voltage is above this level.
This should be set slightly lower than the float
voltage of the charger.
If the charge current is below this percentage
of the battery capacity, the battery can be
considered as fully charged.
The minimum time that the above two
parameters must be met to consider the
battery as fully charged.
If the connection to the temperature sensor is
lost, this value is used in the calculations.
Resets the state of charge manually to 100%.
The name of the battery controller that is used
in the VPN.
Default
Range
value
200 Ah
20-
65535
13.2 V
10-72
4 %
1-10
4 min
1-4
20 ° C
0-50
Battery
Monitor
Step
size
5
0.1
1
1
1