Change Settings; Additional Settings - Lutron Maestro MS-B102 Guia De Instalacion

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Selecting Custom Settings
To display current settings tap the Timeout
( )
(
)
, or PIR Sensitivity
button. The indicator LED
P
setting will illuminate.

Change Settings

1
Press and hold the desired programming button
to flash (about 3 seconds).
2
Tap the same programming button to cycle to your desired setting.
3
Press and hold the same programming button until the
selection (about 3 seconds).
Default settings are shown in bold
IL
Indicator LEDs
Timeout Button
30 minutes
15 minutes
30
15
5 minutes
5
1 minute
1
Sensor Mode Button
Mode
1
Occupancy
(Auto-ON / Auto-OFF)
Occ
2
Occupancy with Learning ALD
Lrn
Occupancy with Fixed ALD
3
Fixd
1
Vacancy
Vac
(Manual-ON / Auto-OFF)
M
Sensor LED
(behind lens) Pulses green for
ultrasonic and amber for PIR
detection during Test mode.
1
Sensor Mode is locked as "Vacancy" in the MS-B102-V (Vacancy model)
2
ALD (Ambient Light Detection) Learn mode will turn lights on only if natural light in room is low. If switch turns on
when there is enough natural light, or if switch does not turn on when there is not enough natural light, press the tap
button within 5 seconds of entering the room. Over time, the switch will learn your preferred setting.
3
ALD (Ambient Light Detection) Fixed mode will turn the lights on only if natural light in room is low. The light level
at which lights will automatically turn on (or stay off) can be adjusted through the "Set ALD Fixed Level" setting in
"Additional Settings" section.
Technical Assistance: www.lutron.com
®
(
)
(
)
, Sensor Mode
M
, Ultrasonic Sensitivity
(
)
that corresponds to the current
IL
( ,
,
)
P
M
or
until an
goes solid to lock your
IL
Tap button
(tap on / off)
Ultrasonic Sensitivity Button
High
Medium
m
Hi
Med
Low
Low
Off
Off
PIR Sensitivity Button
PIR
High
Hi
Medium
Med
Low
Low
Min
Minimum
Ultrasonic
Transducers
PIR Lens
|
U.S.A., Canada, Caribbean: 1.800.523.9466

Additional Settings

Note: All programming options and additional info are available at
www.lutron.com/DTMaestroInstall
Test Mode:
Test Mode is a short timeout (less than 15 seconds) that will test the sensor's coverage with
the current settings.
To enable Test Mode:
begins
1. Press and hold
IL
2. The device will exit Test Mode automatically after 5 minutes of inactivity, or when any button
is pressed.
Note: An amber LED flashes to indicate PIR detection, a green LED flashes to indicate
ultrasonic detection. You may hold
the current sensitivity of that specific technology.
Restore Default Settings:
Press and hold
the sensor's settings back to their defaults.
Off-While-Occupied:
When Off-While-Occupied is Enabled: After manual shutoff, the sensor will keep lights off
as long as the space is occupied and the timeout has not expired. This setting is best for
rooms where presentations are given and lights may be kept off during occupancy. This is
T
the default setting.
When Off-While-Occupied is Disabled: After manual shutoff, the sensor will keep lights off
for 25 seconds before looking for motion. If motion is detected, the lights will turn back on.
This setting is best for high-traffic areas like bathrooms and hallways.
Change Setting:
1. Press and hold
2. Tap
to cycle to your desired setting.
P
3. Press and hold
IL
P
Off-While-Occupied Disabled
Off-While-Occupied Enabled (Default)
Setting Fixed ALD Light Level:
The light level you set will determine when a unit set in "ALD Fixed" sensor mode will turn
lights on, or keep lights off, upon detecting occupancy. This setting only affects the behavior
of a sensor in "ALD Fixed" mode.
Change Setting:
1. Press and hold
2. The Ambient Light Detect light level will now be displayed on the
desired setting.
3. Press and hold
Light Level
IL
High - turns lights ON unless room is very bright
Medium
Low (Default when in ALD Fixed mode)
Minimum - turns lights ON only when room is dark
|
Mexico: +1.888.235.2910
T
until the PIR lens flashes (about 7 seconds).
P
or
for 2 seconds while in test mode to test
and
P
until all
IL
blink slowly (about 7 seconds). This will restore ALL of
and
P
at the same time until an
IL
until the
goes solid to lock your selection.
P
IL
and
until a
begins to flash (about 3 seconds).
M
IL
M
until the
IL
goes solid to lock your selection.
|
Others: +1.610.282.3800
begins to flash (about 3 seconds).
. Tap
M
to cycle to your
IL

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Maestro ms-b102-v

Tabla de contenido