1.6.2 dT monitor...
dT coll/stor
t max coll/stor
dT rturn/supply
1.6.2 dT monitor...
dT return/supply
t max.return/sup.
1.6.4 Emerg.OFF
T limit Coll.1
130.0°C
Hyst
1.7 Login
Access code
Manual mode
1.7.1 Manual m...
Solar pump 1
Solar pump 1
Solar pump 1
›dT monitoring‹ is used to define the criteria which lead
to fault detection. ›dT coll/stor‹ is used to define a
30.0K
differential temperature between collector and tank,
10min
and ›t max.coll/tank‹ for the relevant period of time.
If ›dT coll/stor‹ is exceeded within
30.0K
›t max.coll/tank‹, the controller detects a fault.
Continue to scroll.
The second fault criterion is defined as follows:
›dT return/supply‹ is used to define a differential
temperature between the return and supply flow,
30.0K
›t max return/supply‹, the appropriate period of time.
If ›dT return/supply‹ is exceeded within
›t max return/supply‹, the controller detects a fault.
10min
Continue with ›Coll. Emerg.OFF‹.
›T limit Coll. 1‹ is used to switch OFF the appropriate
solar circuit pumps to prevent destruction.
Under ›Hyst‹, the value is entered by which the limit
5.0K
temperature must be undercut to cancel the forced
shut-off.
Continue with ›Login‹.
365
Continue with ›Manual mode‹.
In manual mode, the individual outputs can be
activated for testing purposes, e. g. to check
that a pump is working properly.
100%
Manual mode can only be exited by pressing ESC.
---
Professional mode
39