Descargar Imprimir esta página

Lutron PowPak RMJS-ECO32-SZ Manual De Installation página 2

Publicidad

Idiomas disponibles

Idiomas disponibles

PowPak | Installation
Programming without a Vive Hub
Control Module with EcoSystem
Part of the Vive Family
Start Here
Associate Wireless Transmitters to
1
PowPak Control Module with
EcoSystem technology
Before beginning this step, make sure that there are no
other PowPak modules being set up within the same
building. It is possible that wireless transmitters from other
systems can be incorrectly associated to this module.
A On the PowPak, hold the Toggle
button " u " for 10 seconds until
lights in the space flash once
every five seconds.
Both LEDs on the module will
begin flashing twice per second.
B Hold the indicated button on each transmitter for
10 seconds until the LED indicator/lens on the
transmitter stops flashing. Please note during this
process the PowPak with flash the load quickly 3
times and the selected transmitter's LED indicator/
lens will flash as well.
Link
Cal.
Test
C On the PowPak, hold the Toggle button " u " for
10 seconds to save association. Lights will return to
high-end and LEDs will stop flashing.
D Permanently install wireless transmitters
(consult individual component installation guides for
information).
Reset Factory Defaults
Note: In some instances, it may be necessary to reset the PowPak
module and connected devices back to factory default settings. Before
beginning, make sure that all devices are connected and powered.
A Rapidly tap the Toggle button " u" on the PowPak three times and hold
on the fourth time until the LED begins to flash at a rate of approx. blinks
every 1 second; then release the Toggle button.
B Within 3 seconds of the start of flashing of the LED on the PowPak,
rapidly tap the Toggle button on the PowPak module three times again.
Make sure to release the Toggle button after the third press.
C The LED will flash at a rate of 2 blink/3 seconds and the connected load
will cycle 3 times to indicate the unit has been reset to factory defaults.
Note: Any associations or programming previously set up with the unit will be
lost and will need to be re-programmed.
Lutron, Pico, Vive, EcoSystem, and PowPak are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. App Store is a trademark of Apple Inc., registered in the U.S. and other countries.
iOS is a registered trademark of Cisco in the U.S. and other countries and is used under license. Android, Google Play and the Google Play logo are trademarks of Google Inc. DALI is a trademark of ZVEI. ©2013 – 2019 Lutron Electronics Co., Inc.
Calibrate the Radio Powr Savr Daylight Sensor
2
Daylight Sensor will control all wired fixtures equally.
A Press and release the "Cal." button on the Daylight Sensor.
B Set lights in room to desired light level.
C Press and hold the "Cal." button for 6 seconds.
D Exit room for 5 minutes to complete calibration.
Note: When calibration has completed, all lights will flash and begin to respond to daylight.
Multiple Daylight Rows (Optional)
For every row of daylighting a separate PowPak Control Module must be used. For detailed setup
refer to the tuning section of the Radio Powr Savr Daylight Sensor installation guide.
• Select the PowPak Control Module that you want to adjust by pressing the Toggle button.
Set a Favorite Light Level
(Optional)
3
For Pico remote controls with a Favorite Button.
A Adjust lights to desired level:
Use the Raise button " " or Lower button " " on the Pico
remote control.
B Save favorite level:
Press and hold the Favorite button for 6 seconds. The load will
flash 3 times to confirm that the Favorite level is saved.
Set Low-End Trim and High-End Trim
4
For best results, minimize the amount of sunlight entering the
room before performing the following procedures.
Notes
Depending on the fixture manufacturer or load, low-end trim and high-end trim may
need to be adjusted.
• Trim low-end to ensure a stable light level because some loads will flicker or drop out
if trimmed too low.
• Be sure that you can turn on the lights to the low-end trim level without any abnormal
operation.
• The factory default high-end trim is suitable for most applications but can be adjusted
as desired.
Low-End Trim
A Enter low-end trim adjustment mode:
Press and hold the Lower button " " on the fixture control for 12 seconds.
The lights will flash and the bottom LED will begin flashing.
B Adjust the low-end trim:
Use the Raise button "
" and Lower button " " on the PowPak Control Module to adjust and set
the lights to the desired low-end (0.1 to 45%).
Note: Low-end depends on the minimum output of connected drivers or ballasts.
C Save the low-end trim:
Press and hold the Toggle button
for 6 seconds to save setting.
" u "
The bottom LED will begin flashing and then turn solid to indicate new level has been saved.
High-End Trim
A Enter high-end trim adjustment mode:
Press and hold the Raise button "
" on the fixture control for 12 seconds.
The lights will flash and the top LED will begin flashing.
B Adjust the high-end trim:
Use the Raise button "
" and Lower button " " on the PowPak Control Module to adjust and set
the lights to the desired high-end (55 to 100%).
C Save the high-end trim:
Press and hold the Toggle button
for 6 seconds to save setting.
" u "
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
5
Link
Cal.
Test
A Enter minimum light level adjustment mode:
B Change the minimum light level:
C Save the minimum light level:
Raise
Lower
Favorite
6
(Optional)
A Set desired occupancy light levels:
B Save occupancy light levels:
Customer Assistance:
TEL: +1.844.LUTRON1
FAX: +1.610.282.1243
www.lutron.com/support
Limited Warranty: www.lutron.com/en-US/ResourceLibrary/warranty/Limited%20Comm.pdf
FCC / IC Information
This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the following
two conditions: (1) This device may not cause interference, and (2) this device must accept any interference, including interference that may cause
undesired operation. Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user's authority to operate this equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
• Re-orient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Customer Assistance www.lutron.com/support
Set Minimum Light Level
(Optional)
Certain applications (e.g., hallways), may require that the lights never turn off. For these areas,
activate Minimum Light Level mode.
Press and hold Toggle button " u " and Lower button " " for 12 seconds. Lights will flash
high-low-high and both LEDs will begin flashing.
If lights stop flashing and turn off, the minimum light level is set to OFF (default).
If lights stop flashing and go to low-end, the minimum light level is ON and set to low-end.
Press Raise button "▲" to set minimum light level to low-end.
Press Lower button " " to set minimum light level to OFF.
Press and hold Toggle button " u " for 6 seconds. Both LEDs will quickly flash to indicate that the
new level has been saved.
Set Occupancy Light Levels
(Optional)
Note: Unoccupied light level is always the minimum light level and cannot be adjusted.
Use the Raise/Lower buttons "▲ / " on the PowPak Control Modules or the Raise/Lower
buttons " / " on associated Pico Remote Controls to adjust lights to the desired level.
Note: Setting lights to OFF during this step will make that control module unaffected by occupancy
(will function as vacancy only).
Press and hold Test button for 6 seconds on any associated Radio Powr Savr Occupancy Sensor
without a Lights On button. Release when Sensor lens starts to flash.