5. The outlet piping should be flexible tubing secured with a hose
clamp (not provided) or pipe (3/8 inch I.D. maximum to prevent
excessive flow back to unit). From condensate unit, extend
discharge piping straight up as high as necessary. Do not
extend this line above the head/GPH of the particular model
being installed. From this high point, slope discharge line
down slightly to a point above drain area; then turn down and
extend to a point below or approximately level with the bottom
of the condensate unit. This will give a siphoning effect which
will improve efficiency of the condensate unit and will, in most
cases, eliminate the need for a check valve (Figure 2). If it is not
possible to slope discharge line down, make an inverted "U"
trap directly above the pump at the highest point.
6. Do not install this pump in a manner that will subject it to
splashing or spraying.
7. Do not install this pump inside air plenums.
ELECTRICAL CONNECTIONS
1. Shut off electrical power at fuse box before making any
connections. All wiring must comply with local codes.
2. Connect power cord to line voltage specified on motor and
nameplate. Power cord must be connected to a constant source
of power (not a fan or other device that runs intermittently).
3. The safety overflow switch should be connected to a Class II
low voltage circuit. To control a thermostatic circuit the COM
and NO connections from the safety switch are to be wired
in series with the low voltage thermostat circuit to shut down
the heating/AC circuit. The COM and NC switch contacts may
be used to actuate a low voltage alarm circuit (connected in
series) if the heating/cooling system can not be disrupted. The
safety switch comes from the factory with leads connected to
the COM and NO switch terminals. Typical hook-up of "NC"
circuits would be (Figures 4 and 5).
TESTING
1. Turn on power.
2. Remove the motor/tank cover assembly and hold it level.
3. Test motor switch by raising motor switch float with finger
(Figure 6). Motor should turn on just before float contacts
cover.
4. Test safety switch by raising safety switch float with finger.
Safety switch should activate before float contacts cover.
5. Replace motor/tank cover assembly on tank.
FIGURE 4
2
This pump is suitable for gas furnace condensate applications.
Caution must be taken to ensure acidity of condensate does
not increase below the average pH of 3.4 (to prevent localized
pocket of acid that acts like a battery causing pitting) by routinely
cleaning or flushing tank with fresh water.
SERVICE INSTRUCTIONS
1. Make certain that the unit is disconnected from the power
source before attempting to service or remove any
component!
2. Be sure the floats move freely. Clean as necessary (Figure 6).
3. Clean the tank with warm water and mild soap.
4. Check the inlet and outlet piping. Clean as necessary. Be sure
there are no kinks in the line that would inhibit flow.
INTRODUCTION
F
Cette feuille d'instructions vous fournit les informations nécessaires
pour entretenir et faire fonctionner votre produit. Conserver ces
directives afin de pouvoir les consulter plus tard.
Le produit que vous avez acheté a été soigneusement fabriqué
avec des matériaux de la plus haute qualité et a été conçu pour
durer longtemps et offrir un service fiable. Les produits sont
soigneusement testés, inspectés et emballés afin d'en assurer la
sécurité de fonctionnement et une livraison en bonne condition.
Vérifier attentivement le produit afin de vous assurer qu'il n'a
pas été endommagé pendant le transport. S'il est endommagé,
veuillez contacter l'entreprise qui vous l'a vendu. Si une réparation
ou un remplacement est requis, elle vous prêtera assistance.
LIRE
ATTENTIVEMENT
PROCÉDER À L'INSTALLATION, À L'UTILISATION OU À
L'ENTRETIEN DU PRODUIT. SE FAMILIARISER AVEC LES
APPLICATIONS, LES LIMITES ET LES RISQUES POTENTIELS
DU PRODUIT. ASSURER SA PROPRE PROTECTION ET
CELLE DES AUTRES EN SUIVANT TOUTES LES RÈGLES
DE SÉCURITÉ. LE NON-RESPECT DE CES DIRECTIVES
PEUT ENTRAÎNER DES BLESSURES ET/OU DES DOMMAGES
MATÉRIELS!
DESCRIPTION
Votre pompe a condensats Red Lion est concue comme une
unite automatique d'evacuation des condensats. Elle evacue
l'eau condensee egouttant de la volute de l'evaporateur d'un
systeme de climatisation. La pomp est actionee par un mechisme
flotteur/ interrupteur lequel entraine le demarrage dela pompe
oorsque environ 2 po 1/4 d'eau s'accumule dans le reservoir. La
pompe s'arrete automatiquement lorsqu'il ne reste plus qu'environ
1 po 1/4 d'eau.
FIGURE 5
CES
DIRECTIVES
AVANT
DE