2
Technical data
Rated data
General electrical data
Area
Input voltage
Output voltage
Brake current
Switching capacity
Breaking energy
Cable protection
Control input
Control voltage
Control current
Protective function
Max. connectable cable
cross−section
Maximum cable length
Operating frequency
Operating times
Service life
Protection against
Overload
Short circuit of the
terminals
Polarity reversal at the
input
1)
Insulation
1)
Brake connection against control card of the controller
38
Values
DC 24 V (18 ... 30 V)
Corresponds to input voltage
0.3 ... 5 A
Max. 110 W
Max. 10 Ws
Recommendation: 7.5 A, tripping characteristic "B" or "C"
Internal
2
2.5 mm
AWG 12
In the chapter "Electrical installation" the dependency of the cable
length on the brake current and the cable cross−section is described.
Max. 6/min
Can be ignored compared to the delay time of the brake.
See documentation of the brake.
> 10 millions of cycles
No
Yes
Yes
Double insulation (EN61800−5−1: V
Separation (UL: V
rated
l
= 300 V AC),
rated
= 500 V AC)
EDK94AZHY DE/EN/FR/ES/IT 2.1