Electrical Installation; Important Notes - Lenze L-force 9400 Instructions De Montage

Module de pilotage du frein de parking
Ocultar thumbs Ver también para L-force 9400:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4

Electrical installation

Important notes

,
During installation the notes given in the documentation for the standard
device must be observed!
(
Stop!
Requirements concerning the brake cable (connection BD1/BD2):
The brake cables must be shielded if they are incorporated in the motor
ƒ
cable.
– Operation with unshielded brake cables can destroy the motor brake
control.
– We recommend the use of Lenze system cables (motor cable with
separately shielded additional cores).
When using a permanent magnet holding brake, ensure the correct
ƒ
polarity of the brake cable.
– If the terminals are reversed, the brake does not release. Since the motor
runs against the closed brake, the brake can be destroyed.
Connect the shield on both sides of PE.
ƒ
Requirements concerning the supply voltage U
The motor brake control must always be supplied with a separate 24 V
ƒ
supply.
– A common supply of the motor brake control and the control card of the
controller is not permissible since otherwise the double insulation
between both components would be reduced.
Set U
ƒ
DC
range and the maximum supply voltage of the motor brake control will not
be exceeded.
)
Note!
The supply status can be reported to the standard device via the error channel.
For further information, please refer to the documentation of the standard
device.
EDK94AZHY DE/EN/FR/ES/IT 2.1
so that the operating voltage of the brake is within the admissible
l
Electrical installation
Important notes
(connection +/−):
DC
4
41

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

E94azhy0101

Tabla de contenido