Descargar Imprimir esta página
Lutron myRoom LV16-120 Instrucciones De Instalación
Lutron myRoom LV16-120 Instrucciones De Instalación

Lutron myRoom LV16-120 Instrucciones De Instalación

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

English
myRoom
TM
Low-Voltage Enclosure
LV16-120
120 V~ 50 / 60 Hz 2 A
Installation Instructions
LV16-230
Please Read Before Installing
220-240 V~ 50 / 60 Hz 2 A
Use these instructions to install the model numbers listed
above.
1. Mount Enclosure (surface-mount only) – Use keyholes
with bolts sufficient for 14 kg (30 lb) load, M6 (1/4 in) bolts
recommend ed (mounting hardware is not provided). Refer to
Figure 1 for enclosure dimensions.
A. Environmental: This equipment is air-cooled via natural
convection. Mount in a location where the vented
cover will not be blocked. 305 mm (12 in) of clearance
in front of the vents is required. This equipment is
intended for indoor use only; in a 0 °C to 40 °C (32 °F to
104 °F) setting with a relative humidity less than 90%,
non-condensing.
B. Sound Requirements: Power supply will hum slightly
while in use. Mount in a location where such noise is
acceptable.
Figure 1 - Enclosure Di men sions
455 mm
(18.0 in)
292 mm
(11.5 in)
343 mm
406 mm
-7°
+7°
(13.5 in)
(16.0 in)
Surface
Mounting
Pedestal (4x)
2. Run power wiring into the enclosure.
!
WARNING — Shock Hazard. Wiring with power on
can result in serious injury or death. To avoid the risk
of electric shock, locate and lock supply breaker in
the OFF position before removing terminal shield.
NOTICE: All wiring must be installed in accordance with
national and local electrical codes.
Input terminal blocks are located under the terminal shield.
Remove the terminal shield to access and wire the terminal
blocks. Locations to run power wiring into the enclosure are
shown in Figure 2. Once terminal shield is removed, refer to
Figure 3 for wiring and torque information.
Technical Assistance:
U.S.A. / Canada: 1.800.523.9466 | Europe: +44.(0)20.7680.4481
Mexico: +1.888.235.2910 | Brazil: +55 (11) 3257-6745 (M-F 8:30 to 17:30 BRT)
Other Countries: +1.610.282.3800
www.lutron.com
Lutron Electronics Co., Inc.
7200 Suter Road, Coopersburg, PA 18036-1299
For increased system reliability, Hospitality Guestroom
Control Units can be powered by an Uninterruptible
Power Supply (UPS) that incorporates surge protection,
brown-out protection, and battery backup. When selecting
a UPS, allow 240 VA of capacity for each control unit on
the UPS. A single large UPS for all control units is better
than an individual UPS for each control unit. This prevents
inconsistent system operation on battery backup if the
individual UPS units power down at different times. The
LV16 does not support housing a UPS. Installation of a UPS
must be done outside this enclosure.
Figure 2 - Power Wiring Locations
Terminal Shield
Line voltage
wire entry
(non-IEC PELV/
NEC
Class 2)
®
Orange Dots "Proc"
Input Power
Switch
Ø 7.9 mm
(0.31 in)
Ø 10.9 mm
(0.43 in)
15.8 mm
(0.63 in)
Figure 3
Terminal Assembly
Black or Brown: Line/Hot input
White or Blue: Neutral input
Yellow / Green: Ground / Earth
Black Wire
– Terminal blocks will accept one 0.75 mm
2
12 AWG) wire or two 0.75 mm
 to 1.5 mm
– Torque terminal blocks from 0.6 N•m to 0.8 N•m (5.3 in-lb to 7.0 in-lb)
Note: Shaded wiring is pre-wired by Lutron. DO NOT REMOVE.
)Lutron and HomeWorks are registered trademarks and myRoom is a trademark of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.
P/N 041488 Rev. A
04/2015
© 2015 Lutron Electronics Co., Inc.
3. Component Installation
Component Installation Locations (Figure 4) – This panel
supports installing up to two Hospitality Guestroom Control
Units or system interfaces in any combination. In addition, it
can house two power supplies and four wire landing boards for
QS Link management.
A . Install the Hospitality Guestroom Control Unit.
— Install the control units in the locations indicated in
Figure 4 using the screws included with the control unit.
The control unit mounting hole locations are indicated by
an orange dot with text "Proc" printed on them (Figure 2).
Peel or puncture the sticker to access the screw holes.
— Torque mounting screws to 1.4 N
B. Install Power Supplies. QSPS-DH-1-60 power supplies are
used to power the control units and the devices wired to the
configurable links on the processor.
— Mount the power supplies on the DIN rail assembly at the
top of the enclosure as shown in Figure 4.
Green Dots "WLB"
— Connect the power cable harness from the Input AC of
the power supply to one of the connectors coming out of
the terminal shield on the left.
— Connect the power cable from the Output DC of the
power supply to the power input of the control unit.
— Connect the black wire to pin 1 (common) and one of the
red wires to pin 2 (P – processor power).
— Connect both of the remaining red wires to pins 3 and 4
(L1 and L2).
NOTE: Refer to the HomeWorks
determining the power requirements for each link based
IEC PELV/NEC
®
Class 2 only
on the link type and the number and type of devices on
the link.
!
Caution — Shock Hazard. May result in serious injury.
To avoid the risk of electric shock or accidental shorts,
cap off any unused wires on this cable.
C. Install Wire Landing Boards. QS-WLB are used to assist
in the wire management of QS link cables wired into the
enclosure.
— Refer to Figure 4 for installation locations of the wire
landing boards.
locations are indicated by green dots with text "WLB"
printed on them
to access the holes.
Use the green WLB label to guide the top left spacer.
For further instruction, refer to the installation guide
included with QS-WLB.
D. Install Interface Devices. Either control unit location shown
in Figure 4 can also accommodate the installation of specific
interface devices.
— Refer to the HomeWorks
which products can be installed in these locations.
— Interface devices are typically powered from the
communication link and not directly from the power
Red Wire
supplies. RF products cannot be installed
in this enclosure.
2
2
 to 4.0 mm
(18 AWG to
2
(18 AWG to 16 AWG) wires
Figure 4
m (12 in-lb) max.
Assembled in U.S.A.
50015757 Rev. A
Example shown with two power supplies, two Hospitality Guestroom Control
Units, and four wire landing boards.
 QS software to assist in
®
4. If there are remaining products to be installed in this
enclosure, leave this instruction sheet in a safe accessible
location.
The wire landing board installation
(Figure
2).
Peel or puncture the sticker
 QS software to determine
®
Warranty:
For LV16-120:
http://www.lutron.com/en-US/ResourceLibrary/warranty/Lim_Warranty_starting_Oct2011.pdf
http://www.lutron.com/TechnicalDocumentLibrary/HomeWorks_Warranty.pdf
For LV16-230:
http://www.lutron.com/en-US/ResourceLibrary/warranty/Limited%20Comm.pdf
http://www.lutron.com/TechnicalDocumentLibrary/HomeWorks_Intl_Warranty.pdf
Component Installation Locations
L(+) N(-)
L(+) N(-)
Power Supply
Mounting Locations
120 - 240 V
24 V
120 - 240 V
24 V
Input / Entrada / Entrée
Output / Salida / Sortie
Input / Entrada / Entrée
Output / Salida / Sortie
22.5 - 25 V
22.5 - 25 V
Guestroom Control Unit
Guestroom Control Unit
GCU-HOSP
GCU-HOSP
lutron.com
lutron.com
+ 1.800.523.9466
+ 1.800.523.9466
+ 44.(0)20.7680.4481
+ 44.(0)20.7680.4481
243C IND. CONT. EQ.
243C IND. CONT. EQ.
IEC PELV / NEC Class 2
IEC PELV / NEC Class 2
®
®
Assembled in U.S.A.
50015757 Rev. A
Control Unit Locations
QS-WLB Locations

Publicidad

loading

Resumen de contenidos para Lutron myRoom LV16-120

  • Página 1 Other Countries: +1.610.282.3800 www.lutron.com )Lutron and HomeWorks are registered trademarks and myRoom is a trademark of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. Lutron Electronics Co., Inc. P/N 041488 Rev. A...
  • Página 2 Otros países: +1.610.282.3800 www.lutron.com )Lutron y HomeWorks son marcas registradas y myRoom es una marca comercial de Lutron Electronics Co., Inc. NEC es una marca registrada de la National Fire Protection Association, Quincy, Massachusetts. Lutron Electronics Co., Inc. P/N 041488 Rev. A...
  • Página 3 Autres pays : +1.610.282.3800 www.lutron.com )Lutron et HomeWorks sont des marques déposées et myRoom est une marque de Lutron Electronics Co., Inc. NEC est une marque déposée de la National Fire Protection Association, Quincy, Massachusetts. Lutron Electronics Co., Inc. P/N 041488 Rev. A...
  • Página 4 Andere Länder : +1.610.282.3800 www.lutron.com )Lutron und HomeWorks sind eingetragene Warenzeichen und myRoom ist ein Warenzeichen von Lutron Electronics Co., Inc. NEC ist eingetragenes Warenzeichen der National Fire Protection Association, Quincy, Massachusetts, USA Lutron Electronics Co., Inc. P/N 041488 Rev. A...
  • Página 5 86.21.61650990 | +44.(0)20.7680.4481 http://www.lutron.com/en-US/ResourceLibrary/warranty/Limited%20Comm.pdf +1.888.235.2910 | +55 (11) 3257-6745 (M-F 8:30 to 17:30 BRT) http://www.lutron.com/TechnicalDocumentLibrary/HomeWorks_Intl_Warranty.pdf +1.610.282.3800 www.lutron.com Lutron, HomeWorks ) Lutron Electronics Co., Inc. P/N 041488 Rev. A 7200 Suter Road, Coopersburg, PA 18036-1299 04/2015 © 2015 Lutron Electronics Co., Inc.

Este manual también es adecuado para:

Myroom lv16-230