INSTRUCTIONS FOR USE
• This device has been created to be integrated into the structure of specially made
sliding gates. The geared motor is fitted with screw type attachments that allow it
to be fitted inside metal profiles.
ASSEMBLY PROCEDURE
The unit may be positioned either to the right or to the left of the passageway.
Respect the following limits:
- 105/SLi924ESB: max. weight 700 kg
- 105/SLi924ELB: max. weight 1000 kg
The builder must make sure that the closing system respects the technical indications
supplied by the standards and laws in force:
- Opening and closing direction mechanical stops;
- Safety devices;
- Correct risk analysis at possible crushing points etc.
See: www.cardin.it - archives - Installation guide and approvals certificates -
MANUAL RELEASE MECHANISM
1
1 - MOTOR RELEASED
- all commands are inhibited
- the gate can be moved by hand
An access slot will have to be built into the column for the release mechanism.
REMOVABLE DRIVE SHAFT
The drive shaft is removable to allow rapid installation and to facilitate the precise
positioning of the geared motor.
ELECTRONIC PROGRAMMER
Electronic control unit for two dc motor with an incorporated encoder and radio
receiver card, which allows the memorisation of 300 user codes. The "rolling code"
type decoder uses 433.92 MHz series transmitters S449. The motor rotation speed is
electronically controlled, starting slowly and increasing in speed; the speed is reduced
as it nears the travel limit so as to enable a controlled smooth stop. Programming is
carried out using the buttons P1, P2, P3, and allows you to set the system, the current
sensor and the entire gate travel distance. The logic carries out position control using
an encoder. The intervention of the anticrush/antidrag sensor during the closing and
opening stages causes travel direction inversion for a few centimetres.
2
2 - RELEASE MEC. REACTIVATED
- all commands are enabled
- the automation will start up again
in the repositioning mode
IMPORTANT REMARKS
Attention! There is no 230 Vac contact on any part of the electronic
card: only low voltage safety current is available. In conformity with the
electrical safety standards it is forbidden to connect binding posts 9
and 10 directly to a circuit that receives power greater than 30 Vac/dc.
Warning! For the correct operation of the programmer the incorporated
batteries must be in good condition: the programmer will lose the
position of the gate in case of blackouts when the batteries are flat
the alarm will sound.
Check the good working order of the batteries every six months (see
page 19 "Battery check").
• After having installed the device, and before powering up the program-
mer, release the door (manual release mechanism) and move it manually,
checking that it moves smoothly and has no unusual points of resistance.
• The controlled load output (binding post 15) is aimed at reducing battery
power consumption (if installed) during blackouts; photocells and other
safety devices should be connected to this output.
• When a command is received, via radio or via wire, the electronic program-
mer routes voltage to the CTRL 24 Vdc output. It then evaluates the state
of the safety devices and if they are at rest it will activate the motor.
• Connecting devices to the controlled output contact also allows you to
carry out the autotest function (enabled using "TEST FI" and "TEST FS" in
the "OPTIONS" menu) and check that the safety devices are functioning
correctly.
• The presence of the electrical current sensor does not dispense with the
obligation to install photoelectric cells and other safety devices foreseen by
the safety standards in force.
• Before connecting the appliance make sure that the voltage and frequency
rated on the data plate conform to those of the mains supply.
• For the 230 Vac power supply only use a 2 x 1.5 mm
• The cable may only be replaced by qualified technicians.
• An all pole trip switch with at least 3 mm between the contacts must be
installed between the unit and the mains supply.
• Don't use cables with aluminium conductors; don't solder the ends of cables
which are to be inserted into the binding posts; use cables marked T min
85°C and resistant to atmospheric agents.
• The terminal wires must be positioned in such a way that both the wire and
the insulating sheath are tightly fastened (a plastic jubilee clip is sufficient).
POWER SUPPLY CONNECTION
• Connect the control and security device wires.
• Run the mains power supply to the separate two-way
terminal board that is already connected to the trans-
former.
Motor - encoder and terminal board connections
• You must scrupulously respect the motor connection sequence between the
motors and the programmer. The order of the binding post connections 1 to 7 is
identical on both;
- connect the wires of motor, the encoder
and the release mechanism to the main
board of the electronic programmer using
the terminal block;
- connect the prewired terminal "LOG" to
the motor terminal block "MOT".
14