Functions – Certain functions may be modified on the board
through the CN4 jumpers:
Jumper 1-8 = Program. DO NOT TOUCH. (On by default)
Jumper 2-7 = Activation temperature for battery.
On - 15ºC. Off - 10ºC (default).
Jumper 3-6 = Kick-up air flow 10% if T > 19ºC.
On – Kick up (default). Off – no kick up
Jumper 4-5 = Stop if T > 25ºC.
On - stop (default for PIV).
Off – non-stop (default for PIV W).
Time counter - counts the number of hours in use up to 11 years.
Hold the button down to see all the numbers from largest to
smallest.
Speed options- 4 settings: Trickle, Medium, Large and Boost,
indicated by LEDs: green, yellow, orange and red.
Temperature display- regardless of the chosen configuration, the air supply temperature is
shown on 3 LEDs: T <19ºC (yellow), >19ºC (orange), >25ºC (red). If the temperature is on the
limit, the LEDs may flash.
Access- To access the board, remove the two screws from the circular plastic cover. For the PIV W
model, you must detach the duct and remove the exterior housing.
CIRCUIT BOARD
7
Products: PIV, PIV BP and PIV W
ANNEX
DANGER, MAINS VOLTAGE!
Make sure you wear hand
protection before handling
connectors (4 and 7)
1. Time elapsed button
2. Time elapsed display
3. Functions legend
4. Function jumpers
5. Speed button
6. LED speed indicator
7. Voltage
8. LED temperature indicator
8
1
2
3
4
Default configuration PIV
1
2
3
4
Default configuration PIV W
8 ON Program
7 OFF Battery 10ºC
6 ON Kick up
5 ON Stop >25ºC
8 ON Program
7 OFF Battery 10ºC
6 ON Kick up
5 OFF Stop >25ºC