Broan-NuTone RANGEMASTER 61000 Serie Manual Del Usuario página 5

Ocultar thumbs Ver también para RANGEMASTER 61000 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTALL THE DUCTWORK
NOTE: To reduce the risk of fire, use only metal
ductwork.
1. Decide where the ductwork will run between
the hood and the outside.
2. A straight, short duct run will allow the hood
to perform most efficiently.
3. Long duct runs, elbows, and transitions will
reduce the performance of the hood. Use
as few of them as possible.
4. Install a roof or wall cap. Connect 6" round
metal ductwork to cap and work back
towards hood location. Use duct tape to seal
the joints between ductwork sections.
INSTALL MOUNTING
BRACKETS
1. Construct wood wall framing that is flush
with interior surface of wall studs.
Make sure:
a) the framing is centered over installation
location.
b) the height of the framing will allow the
mounting brackets to be secured to the
framing within the dimensions shown.
2. After wall surface is finished, secure
mounting brackets to framing using
dimensions shown.
NOTE:
- On 8' ceilings, the hood distance above cook top is :
minimum 24", maximum 27-1/2".
- On 9' ceilings, the hood distance above cook top is :
- minimum 27", maximum 30" (for Ducted Configuration).
- minimum 24", maximum 30" (for Non-Ducted Configuration).
ROOF CAP
DECORATIVE
FLUE
HOOD
24" TO 30" ABOVE
COOKING SURFACE
FRAMING BEHIND DRYWALL
bottom of hood
29
/
"=
13
16
bottom of hood
35
/
"=
13
16
- 5 -
6" ROUND
DUCT
WALL
CAP
6" ROUND
ELBOW
above cooktop
24"
above cooktop
30"

Publicidad

Tabla de contenido
loading

Tabla de contenido