Technical Specifications - Johnson Controls VP140 Instrucciones De Instalación

Ocultar thumbs Ver también para VP140:
Tabla de contenido

Publicidad

Technical Specifications

Flow rate max.
Service
Accuracy up to 15 PSID = 100 kPa
Minimum ΔP for start-up
Maximum ΔP
Maximum working pressure
Close off pressure
Temperature
Connection
Leakage
Compliance
Flow rate max.
Service
Accuracy up to 15 PSID = 100 kPa
Minimum ΔP for start-up
Maximum ΔP
Maximum working pressure
Close off pressure
Temperature
Connections
Leakage
Compliance
Table 9: VP140Lxx
VP140LCA
1.6 GPM, 360 l/h
Water or water-glycol mixture (up to 50% glycol), quality to VDI 2035
Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and other relevant provisions of
the PED (Pressure Equipment Directive)
Table 10: VP140Mxx
VP140MAG
3.4 GPM, 780 l/h
Water or water-glycol mixture (up to 50% glycol), quality to VDI 2035
Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and other relevant provisions of
the PED (Pressure Equipment Directive)
VP140LCB
3.0 GPM, 600 l/h
± 5%
2.9 psi
20 kPa
58 psi
400 kPa
360 psi
2,482 kPa
200 psi
1,379 kPa
14 to 248 °F
-10 to 120 °C
½" FNPT
Class IV IEC 60534-4
VP140MCC
5.0 GPM, 1,150 l/h
± 5%
3.6 psi
25 kPa
58 psi
400 kPa
360 psi
2,482 kPa
200 psi
1,379 kPa
14 to 248 °F
-10 to 120 °C
¾" FNPT
Class IV IEC 60534-4
10
VP140LAJ
4.4 GPM, 1,000 l/h
VP140MAU
9.7 GPM, 2,200 l/h
4.4 psi
30 kPa
¾" FNPT Union
P/N 14-88360-03419, Rev. –

Publicidad

Tabla de contenido
loading

Tabla de contenido